Chapter 7 System Operation And Maintenance 45
Liebert.CRV+ Series Air Cooled Precision Air Conditioner User Manual
Chapter 7 System Operation And Maintenance
This chapter expounds the system operation and maintenance of the Liebert.CRV+ air-cooled series air conditioner,
including system self-diagnosing test, and maintenance of filter, fan kit, electrode humidifier, electrical heater, drain
system and refrigerant system.
Risk of electric shock. Can cause injury or death.
Disconnect local and remote power supplies before working within.
Before proceeding with installation, read all instructions, verify that all the parts are included and check the
nameplate to be sure the voltage matches available utility power.
Follow all local codes.
7.1 Routine Maintenance And Inspection(monthly)
Components listed below are required to be checked or inspected monthly, mainly on functionality and wearing
symptoms. The inspection items are shown in Table 7-1.
Table 7-1 Monthly routine inspection items
Components
Item
Remark
Filter
Check for clogging or damage
Check the filter clogging switch
Clean the filter
Fan
Fan blades are not distorted
The bearings are not worn out
Compressor
Check for leakage
Listen to the operation sound, observe the operation vibration
Air cooled condenser
Make sure condenser coil is clear from dirt and debris. Clean if required.
The fan base should be firm
The fan vibration absorber is not deteriorated or damaged
The SPD board should be effective (in the storming seasons, the SPD
board should be check once a week)
The refrigerant pipes are properly supported
Refrigeration system
Check the suction pressure
Check the discharge pressure
Check refrigerant pipes for sign of leaks
Check the moisture condition in system through the sight glass
Check the electronic expansion valve
Heating system
Check the re-heater operation
Check the erosion situation of the components
7.2 Routine Maintenance And Inspection (Half yearly)
Half yearly check the items as shown in Table 7-2.
Table 7-2 Half yearly routine inspection items
Components
Item
Remark
Air Filter
Check for clogging or damage
Check the filter clogging switch
Clean the filter
Fan
Fan blades are not distorted
The bearings are not worn out
Check and fasten the circuit connections