AGL_Ref_ST_ZO_E_Rev00
19
Power circuit
Control circuit
Legend
B1 ................. System controller
F4 ........ LP switch
Q1 ................. Main switch
K2 ........ Contactor
D ................... Drive assembly
RCD .... Residual current device type B or B+
F1, F6/7/8 ..... Fuses
S1 ........ Auxiliary switch
F3 .......
……...HP limiter
Grey = optional, depending on the drive type
Figure 21: Wiring diagram for ZOV*AG with three-phase drive
4.3 Terminal box
CAUTION
Mechanical stress or shock! Overheating! Terminal Fusite damage and
leakage!
Mechanical stress and shocks to the Fusite must be avoided as they
could damage the glass and/or ceramic. This might result in hermeticity failure
or loss of terminal performance. Precautions are required to prevent striking
or bending of pins. Bent or damaged pins may result in loss of hermeticity
and/or terminal performance.
Ensure correct connection of cables to the compressor terminal Fusite to avoid
local overheating of Fusite pins which might lead to refrigerant leaks.
Cable glands have an influence on the protection class of the terminal box. Emerson strongly
recommends using appropriate cable glands according to EN 50262 in order to reach the rated
protection class. An example of correct electrical installation is shown in
Figure 20
below.
The standard terminal box is IP54 for the compressor models ZO(V)*AG.
Figure 22: Terminal box IP54 and correct electrical installation with cable gland