Electrical connection
4.1 General recommendations
WARNING
Electrical hazard! Serious personal injuries and/or system breakdown!
The compressor must always have the ground wire attached to the
compressor terminal fence. The other end of the ground wire must be
connected to the appropriate ground terminal on the drive.
Disconnect and lock out power before servicing. Allow drive components to
electrically discharge before servicing. Respect the time according to drive
manual before servicing the drive. Use compressor with grounded system
only. Refer to original equipment wiring diagrams. Electrical connections must
be made by qualified electrical personnel.
CAUTION
High voltage! Drive damage!
An optional unit contactor must be installed
upstream of the drive, not between the drive and the compressor. Nor should
a disconnected switch be installed between the drive and the compressor.
Major faults and irreversible damage to the drive could occur if the drive output
is open-circuit while the compressor is running.
Before connecting the drive to the power network, make sure that all the cables to and from the drive
and to the compressor are correctly connected and that the supply voltage, phases and frequency
match the drive nameplate data.
Wiring should remain physically separated to minimize the introduction of electrical noise.
Before connecting the compressor, ensure the supply voltage, the phases and the frequency match
the nameplate data.
For safety reasons, Emerson recommends that the electrical installation be executed in compliance
with standard EN 60335-1 and/or other standards and regulations of application. The wiring must
conform to local regulations and codes of practice.
NOTE: The drive assembly contains accessories such as chokes and EMC filters, which are
part of the drive. For detailed list and description please refer to the EVM/EVH Drive User
Manual.
4.2 Electrical wiring
WARNING
Conductor cables! Electrical shock!
Shut off power supply before
undertaking any task on electrical equipment.
For recommended wiring diagrams, see Error! Reference source not found..
The combination of ZOV*AG compressors and inverters can cause earth leakage currents, both AC
and DC, due to the presence of the inverter and an EMC filter in the system. Therefore an AC/DC-
sensitive residual current device (RCD) must be used on the power supply side. The RCD can be
either type B or B+.
NOTE: For recommendations about the EMC and details about wiring up the drive assembly,
please refer to the EVM/EVH User Manual.