a.
Stream Compressors
-
All Stream compressors are suction gas cooled. (motor is cooled by refrigerant gas
that is led over the motor).
-
All compressors are fitted with discus valve plates.
-
Each cylinder head has 2 plugged 1/8" - 27 NPTF tapped holes for connecting high
pressure switches.
-
Copeland Stream compressors is fitted with CoreSense module as a standard.
b. Liquid Receiver
-
Emerson CDUs are equipped with liquid receivers
-
Rotalock service valve is provided at the receiver outlet
-
Sight glass mounted on liquid receivers to help to not exceed maximum liquid level
c.
HP/LP Cut-out
-
Dual HP/LP, auto reset, safety switch
-
Pressure switches used for control/protective functions
-
Control functions – compressor cycling, pump down
-
Protective functions – pressure limiting and cut-out against excessive pressures,
against loss of charge or freeze protection
-
Display scales are printed in relative pressure units – “bar” and “psi”
d. Z9/Z12 Condenser
-
Condenser is constructed with copper tubes and aluminum fins, steel-sheet housing
with a fan opening.
-
Number of fans: 4
e. Fan
-
Z9 CDU is equipped with single phase fans and dual rated for 50/60 Hz operation.
-
Fan is made of an external rotor motor with fan blades permanently fixed to rotor.
-
Fan guard has 4 mounting feet.
-
Fan is positioned in order to blow air from condenser to the compressor.
7