Figure 5
Scroll Wiring Schematic
Typical Solid State Timer
Discharge Line
Thermostat
Compressor
Contactor
Coil
Other Protective
Devices (if used)
System Operating
Thermostat
Fuse
(Optional)
Condenser Fan
Contactor Coil
(if used)
Time Delay Relay Specifications
Timer Opens: 1 Electrical Cycle
(.016 Seconds with 60 HZ Operation)
After Power is Removed
Timer Closes: 2 Minutes (+/- 20%) Later,
Whether Power is Restored or Not
CSR = Current Sensing Relay
Contact
230/240 VAC
C2
C1