background image

14

© 2015 Emerson Climate Technologies, Inc.

AE4-1365 R4

Copeland Scroll compressors are designed for use 

with refrigerant, and testing with nitrogen may result 

in a situation where the compressor does not develop 

a pressure differential (no pump condition). When 

testing with nitrogen, the compressor must be allowed 

to cool for several minutes between tests.

Single phase scrolls with an electrical nomenclature 

of “PFV” (208-230 volt, 1Ø, 60 Hertz) at the end of 

the model number are guaranteed to start at 187 volts 

or higher and must have a voltage no lower than 197 

volts once the compressor is running under load. All 

other compressor voltages, both single and three 

phase, 50 & 60 Hertz are guaranteed to start and 

run at 10% below the lowest voltage shown on the 

nameplate.

Variable transformers used on assembly lines are often 

incapable of maintaining the starting voltage when 

larger compressors are tested. To test for voltage sag 

during  starting,  the  first  compressor  in  a  production 

run should be used to preset the voltage. Remove the 

start wire from the compressor and apply 200 volts to 

the compressor. With the start winding removed, the 

compressor will remain on locked rotor long enough 

to read the supply voltage. If the voltage sags below 

the minimum guaranteed starting voltage, the variable 

transformer must be reset to a higher voltage. When 

discussing this starting amperage it should be noted 

that “inrush current” and locked rotor amps (LRA) are 

one and the same. The nameplate LRA is determined 

by physically locking a compressor and applying the 

highest nameplate voltage to the motor. The amperage 

that the motor draws after four seconds is the value 

that is used on the nameplate. Since there is a direct 

ratio between voltage and locked rotor amperage, the 

lower the line voltage used to start the compressor, 

the lower the locked rotor amperage will be.

Unbrazing System Components

WARNING

Before attempting to braze, it is important to 

recover all refrigerant from both the high and low 

side of the system.

If the refrigerant charge is removed from a scroll-

equipped unit by recovering one side only, it is very 

possible that either the high or low side of the system 

remains pressurized. If a brazing torch is then used 

to disconnect tubing, the pressurized refrigerant and 

oil mixture could ignite when it escapes and contacts 

the  brazing  flame.  Instructions  should  be  provided 

in appropriate product literature and assembly (line 

repair) areas. If compressor removal is required, the 

compressor should be cut out of the system rather 

than unbrazed. See 

Figure 7

 for proper compressor 

removal procedure.

SERVICE PROCEDURES
Copeland Scroll Compressor Functional Check

A functional compressor test during which the suction 

service valve is closed to check how low the compressor 

will pull the suction pressure is not a good indication 

of how well a compressor is performing. 

NOTICE

 

Such a test will damage a scroll compressor in 

a few seconds. 

The following diagnostic procedure 

should be used to evaluate whether a Copeland Scroll 

compressor is functioning properly:

1. 

Proper voltage to the unit should be verified.

2.  Determine if the internal motor overload has 

opened or if an internal motor short or ground 

fault has developed. If the internal overload has 

opened, the compressor must be allowed to cool 

sufficiently to allow it to reset.

3.  Check that the compressor is correctly wired.

4.  Proper indoor and outdoor blower/fan operation 

should be verified.

5.  With service gauges connected to suction 

and  discharge  pressure  fittings,  turn  on  the 

compressor. If suction pressure falls below normal 

levels the system is either low on charge or there 

is a flow blockage in the system.

6.  Single phase compressors

 – If the compressor 

starts and the suction pressure does not drop 

and discharge pressure does not rise to normal 

levels, either the reversing valve (if so equipped) 

or the compressor is faulty. Use normal diagnostic 

procedures to check operation of the reversing 

valve. 

Three phase compressors

 – If suction 

pressure does not drop and discharge pressure 

does not rise to normal levels, reverse any two of 

the compressor power leads and reapply power 

to make sure the compressor was not wired to 

run in reverse. If pressures still do no move to 

normal values, either the reversing valve (if so 

equipped) or the compressor is faulty. Reconnect 

the  compressor  leads  as  originally  configured 

Содержание Copeland Scroll ZP K3 Series

Страница 1: ...ction Line Noise Vibration 8 Mounting Parts 9 Electrical Connections 9 Deep Vacuum Operation 9 Shell Temperature 9 Suction Discharge Fittings 9 System Tubing Stress 9 Three Phase Scroll Electrical Phasing 9 Brief Power Interruptions 10 Manifolding Tandem Compressors 10 Tandem Applications 10 Application Tests Application Summary 10 Continuous Floodback Test 11 Field Application Test 11 Assembly Li...

Страница 2: ...ssor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which if not avoided could result in...

Страница 3: ...ety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system commponents Personal safety equipment must be used Failure to follow these warnings could result in serious personal...

Страница 4: ...fer to the on line product information at EmersonClimate com for details APPLICATION CONSIDERATIONS The following application guidelines should be considered in the design of a system using ZP K3 ZP KC and ZP KW scroll compressors Some of the guidelines are recommended in this bulletin for good practice or best in class other guidelines must be followed to ensure a safe and reliable application Th...

Страница 5: ...in oil pump out and eventual bearing failure A cut out setting no lower than 20 psig 1 4 bar is recommended Discharge Line Thermostat Some systems such as air to air heat pumps may not work with the above low pressure control arrangement A discharge line thermostat set to shut the compressor off before the discharge temperature exceeds 260 F 125 C may have to be used to achieve the same protection...

Страница 6: ...ring heating may not require an accumulator if testing assures the system designer that there will be no flood back throughout the operating range To test for flood back conditions and determine if the accumulator or TXV design is adequate please see the Application Tests section The accumulator oil return orifice should be from 040 to 055 inches 1 1 4mm in diameter depending on compressor size an...

Страница 7: ...h the minimum run time obtain a sample compressor equipped with a sight tube available from Emerson and install it in a system with the longest connecting lines that are approved for the system The minimum on time becomes the time required for oil lost during compressor startup to return to the compressor sump and restore a minimal oil level that will assure oil pick up through the crankshaft Cycl...

Страница 8: ...ing processes that leave solid or liquid contaminants in the evaporator coil condenser coil and interconnecting tubing plus any contaminants introduced during the field installation process Molecular sieve and activated alumina are two filter drier materials designed to remove moisture and mitigate acid formation A 100 molecular sieve filter can be used for maximum moisture capacity A more conserv...

Страница 9: ...internal suspension and can be easily avoided by using standard suction line isolation techniques as described in Table 2 The sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends Mounting Parts Table 4 lists the mounting parts to be used with these compressors Many OEM customers b...

Страница 10: ...reverse will sometimes make an abnormal sound There is no negative impact on durability caused by operating three phase Copeland Scroll compressors in the reversed direction for a short period of time under one hour After several minutes of reverse operation the compressor s internal overload protector will trip shutting off the compressor If allowed to repeatedly restart and run in reverse withou...

Страница 11: ... for any unit where both the design system charge is higher than the compressor refrigerant charge limit listed in Table 3 and a capillary tube fixed orifice or bleed type TXV is used on either the indoor or the outdoor coil of the unit Continuous Floodback Test It is expected that the design would not flood during standard air conditioning operation Running a partially blocked indoor air filter o...

Страница 12: ...lined above for the appropriate application tests ASSEMBLY LINE PROCEDURES Installing the Compressor WARNING Use care and the appropriate material handling equipment when lifting and moving compressors Personal safety equipment must be used Copeland Scroll compressors leave the factory dehydrated withadryairholdingcharge Ifcompressors are stored in a cold ambient i e outside during the winter the ...

Страница 13: ...onal charge is needed it should be added as liquid to the low side of the system with the compressor operating Pre charging on the high side and adding liquid on the low side of the system are both meant to protect the compressor from operating with abnormally low suction pressures during charging NOTICE Do not operate the compressor without enough system charge to maintain at least 55 psig 3 8 ba...

Страница 14: ...ng one side only it is very possible that either the high or low side of the system remains pressurized If a brazing torch is then used to disconnect tubing the pressurized refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame Instructions should be provided in appropriate product literature and assembly line repair areas If compressor removal is required the comp...

Страница 15: ...ecommendations NOTICE It is highly recommended that the suction accumulator be replaced if the system contains one This is because the accumulator oil return orifice or screen may be plugged with debris or may become plugged shortly after a compressor failure This will result in starvation of oil to the replacement compressor and a second failure The system contactor should be inspected for pitted...

Страница 16: ... ng Temperature C Condensing Temperature C Condensing Temperature F Evapora ng Temperature F 29 19 9 1 11 21 31 4 14 24 34 44 54 64 40 50 60 70 80 90 100 110 120 130 140 150 160 20 10 0 10 20 30 40 50 60 70 80 90 Evaporating Temperature C Condensing Temperature C Condensing Temperature F Evaporating Temperature F ZP KW Pool Envelope ZP K3 ZP KC Envelope Figure 1a Operating Envelope Figure 1b Opera...

Страница 17: ...mpressor Sump Temperature F Evaporating Temperature F 200 F 93 3 C Max Oil Temp Acceptable Unacceptable Too Much Refrigerant Dilu on See Note 1 Note 1 Operation in this refrigerant dilution area is safe in air to air heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Figure 2 ...

Страница 18: ... Label Figure 4 Crankcase Heater Connect the heater so that the connection point straddles the compressor seam weld ZP50 57K3 ZP61 143KC ZP70 83KW Seam Weld WARNING Verify the correct crankcase heater voltage for the application and ensure heater is properly grounded ...

Страница 19: ...e Discharge Manifold Assembly Suction Manifold Assembly Mounting Rail 2 Required Compressor to Rail Mounting Kit Tandem to Unit Mounting Kit Figure 5 Typical ZP KC Tandem 12 Min Tilt the Compressor a Minimum of 12 for Installation of the Oil Equalization Line Oil Equalization Line Figure 6 Tilted Tandem ...

Страница 20: ...evenly Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result Field Service WARNING Remove refrigerant ...

Страница 21: ...21 2015 Emerson Climate Technologies Inc AE4 1365 R4 Figure 8 ...

Страница 22: ...fler Not required Alternate Configuration Component Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Mass Suction muffler May be required Acts as dampening mass Table 2 Design Configurations Table 3 Compressor Refrigerant Charge Limits Model Frame Size Charge Limit 120 x Limit Tandem Charge Limit Pounds kg Pounds kg Pounds kg ZP50 57K3 ZP70 83KW...

Страница 23: ...case Heater 277V 70W 018 0095 09 21 Leads Crankcase Heater Junction Box 998 7024 00 All Models Terminal Cover 005 1213 00 ZP50 57K3 ZP61 91KC ZP70 83KW Terminal Cover Gasket 020 0964 00 Terminal Cover 005 1494 00 ZP104 143KC Terminal Cover Gasket 020 1390 00 Terminal Block 021 0227 03 ZP104 143KC All Voltages Terminal Block 021 0234 00 ZP50 57K3 ZP61 91KC ZP70 83KW 230 Volt Only Terminal Block 021...

Страница 24: ...1 1 Phase Only Comfort Alert Module 543 0038 02 All Models 3 Phase Only Discharge Line Thermostat 998 7022 02 ZP50 57K3 ZP61 83KC Fits 1 2 Tube Discharge Line Thermostat not available ZP91KC Fits 3 4 Tube Discharge Line Thermostat 998 0071 02 ZP104 143KC Fits 7 8 Tube Discharge Rotalock Pipe Plug 036 0008 16 ZP104 143KC 1 8 27 NPTF Discharge Rotalock O Ring Seal 028 0028 00 ZP50 57K3 ZP61 83KC Dis...

Страница 25: ...required per tandem Includes bolts washers and steel spacers Tandem Mounting Kit Rails To Unit 527 0150 00 ZPT100 114K3 ZPT122 182KC Includes sleeves washers and grommets 35 45 durometer Tandem Mounting Kit Rails To Unit 527 0177 00 ZPT208 286KC Includes sleeves washers and grommets 65 75 durometer Tandem Rail 074 1235 00 ZPT100 114K3 ZPT122 182KC 2 rails required per tandem Tandem Rail 574 0053 0...

Отзывы: