background image

6

© 2015 Emerson Climate Technologies, Inc.

AE4-1365 R4

use a shutdown valve located on the muffler plate to 

perform the same function.  Neither valve is considered 

to have a low leak rate suitable for recycling pumpdown.  

Motor Overload Protection

Conventional internal line break motor overload 

protection is provided. The overload protector opens the 

common connection of a single-phase motor and the 

center of the Y connection on three-phase motors. The 

three-phase overload protector provides primary single-

phase protection. Both types of overload protectors 

react to current and motor winding temperature.

Operating Envelope

The ZP model family is approved, and U.L. recognized, 

for use with R-410A only. See 

Figures 1a and 1b

 

for the R-410A operating envelope. The envelope 

represents safe operating conditions with 20F° (11K) 

superheat in the return gas. Please note that the ZP*KW 

compressors have a smaller envelope for swimming 

pool applications.

Power Supply

All motors for the ZP compressors, whether single 

or three phase, with the exception of the “PFV” 208-

230, 1Ø, 60 Hz motor, are designed to operate within 

a voltage range of +/-10% of the voltages shown on 

the nameplate. For example, a compressor with a 

nameplate voltage of 200-230 volts can start and 

operate within a range of 180-253 volts. Compressors 

with a “PFV” designated motor such as ZP50K3E-

PFV, may only be operated in a range of 197-253 volts 

under maximum load conditions.

Accumulators

The use of accumulators is very dependent on the 

application. The Copeland Scroll compressor’s inherent 

ability to handle liquid refrigerant during occasional 

operating  flood  back  situations  make  the  use  of  an 

accumulator unnecessary in standard designs such 

as condensing units. Applications such as heat pumps 

with orifice refrigerant control that allow large volumes 

of  liquid  refrigerant  to  flood  back  to  the  compressor 

during normal steady-state operation can dilute the 

oil to such an extent that bearings are inadequately 

lubricated, and wear will occur. In such a case an 

accumulator  must  be  used  to  reduce  flood  back  to 

a safe level that the compressor can tolerate. Heat 

pumps designed with a TXV to control refrigerant 

during heating may not require an accumulator if 

testing assures the system designer that there will 

be  no  flood  back  throughout  the  operating  range. 

To  test  for  flood  back  conditions  and  determine  if 

the accumulator or TXV design is adequate, please 

see the 

Application Tests

 section. The accumulator 

oil return orifice should be from .040 to .055 inches 

(1 – 1.4mm) in diameter depending on compressor 

size and compressor flood back results. A large-area 

protective screen no finer than 30x30 mesh (0.6mm 

openings) is required to protect this small orifice from 

plugging. Tests have shown, that in the presence of 

very fine debris, a small screen with a fine mesh can 

easily become plugged causing oil starvation to the 

compressor bearings. The size of the accumulator 

depends upon the operating range of the system 

and the amount of sub cooling and subsequent head 

pressure allowed by the refrigerant control. System 

modeling indicates that heat pumps that operate down 

to and below 0°F (-18°C) will require an accumulator 

that can hold around 70% to 75% of the system 

charge. Behavior of the accumulator and its ability 

to prevent liquid slugging and subsequent oil pump-

out at the beginning and end of the defrost cycle 

should be assessed during system development. This 

will require special accumulators and compressors 

with sight tubes and/or sight glasses for monitoring 

refrigerant and oil levels.

Screens

Screens  finer  than  30x30  mesh  (.06mm  openings) 

should not be used anywhere in the system with 

these compressors. Field experience has shown 

that  finer  mesh  screens  used  to  protect  thermal 

expansion valves, capillary tubes, or accumulators 

can become temporarily or permanently plugged with 

normal system debris and block the flow of either oil 

or refrigerant to the compressor. Such blockage can 

result in compressor failure.

Crankcase Heat - Single Phase

A crankcase heater is 

recommended

 on single 

phase compressors when the system charge amount 

exceeds the limit shown in 

Table 3

. A crankcase heater 

is 

required

 for systems containing more than 120% of 

the compressor refrigerant charge limit listed in 

Table 

3

. This includes long line length systems where the 

extra charge will increase the standard factory charge 

above the 120% limit.

Experience  has  shown  that  compressors  may  fill 

with liquid refrigerant under certain circumstances 

and  system  configurations,  notably  after  long  off 

Содержание Copeland Scroll ZP K3 Series

Страница 1: ...ction Line Noise Vibration 8 Mounting Parts 9 Electrical Connections 9 Deep Vacuum Operation 9 Shell Temperature 9 Suction Discharge Fittings 9 System Tubing Stress 9 Three Phase Scroll Electrical Phasing 9 Brief Power Interruptions 10 Manifolding Tandem Compressors 10 Tandem Applications 10 Application Tests Application Summary 10 Continuous Floodback Test 11 Field Application Test 11 Assembly Li...

Страница 2: ...ssor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which if not avoided could result in...

Страница 3: ...ety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system commponents Personal safety equipment must be used Failure to follow these warnings could result in serious personal...

Страница 4: ...fer to the on line product information at EmersonClimate com for details APPLICATION CONSIDERATIONS The following application guidelines should be considered in the design of a system using ZP K3 ZP KC and ZP KW scroll compressors Some of the guidelines are recommended in this bulletin for good practice or best in class other guidelines must be followed to ensure a safe and reliable application Th...

Страница 5: ...in oil pump out and eventual bearing failure A cut out setting no lower than 20 psig 1 4 bar is recommended Discharge Line Thermostat Some systems such as air to air heat pumps may not work with the above low pressure control arrangement A discharge line thermostat set to shut the compressor off before the discharge temperature exceeds 260 F 125 C may have to be used to achieve the same protection...

Страница 6: ...ring heating may not require an accumulator if testing assures the system designer that there will be no flood back throughout the operating range To test for flood back conditions and determine if the accumulator or TXV design is adequate please see the Application Tests section The accumulator oil return orifice should be from 040 to 055 inches 1 1 4mm in diameter depending on compressor size an...

Страница 7: ...h the minimum run time obtain a sample compressor equipped with a sight tube available from Emerson and install it in a system with the longest connecting lines that are approved for the system The minimum on time becomes the time required for oil lost during compressor startup to return to the compressor sump and restore a minimal oil level that will assure oil pick up through the crankshaft Cycl...

Страница 8: ...ing processes that leave solid or liquid contaminants in the evaporator coil condenser coil and interconnecting tubing plus any contaminants introduced during the field installation process Molecular sieve and activated alumina are two filter drier materials designed to remove moisture and mitigate acid formation A 100 molecular sieve filter can be used for maximum moisture capacity A more conserv...

Страница 9: ...internal suspension and can be easily avoided by using standard suction line isolation techniques as described in Table 2 The sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends Mounting Parts Table 4 lists the mounting parts to be used with these compressors Many OEM customers b...

Страница 10: ...reverse will sometimes make an abnormal sound There is no negative impact on durability caused by operating three phase Copeland Scroll compressors in the reversed direction for a short period of time under one hour After several minutes of reverse operation the compressor s internal overload protector will trip shutting off the compressor If allowed to repeatedly restart and run in reverse withou...

Страница 11: ... for any unit where both the design system charge is higher than the compressor refrigerant charge limit listed in Table 3 and a capillary tube fixed orifice or bleed type TXV is used on either the indoor or the outdoor coil of the unit Continuous Floodback Test It is expected that the design would not flood during standard air conditioning operation Running a partially blocked indoor air filter o...

Страница 12: ...lined above for the appropriate application tests ASSEMBLY LINE PROCEDURES Installing the Compressor WARNING Use care and the appropriate material handling equipment when lifting and moving compressors Personal safety equipment must be used Copeland Scroll compressors leave the factory dehydrated withadryairholdingcharge Ifcompressors are stored in a cold ambient i e outside during the winter the ...

Страница 13: ...onal charge is needed it should be added as liquid to the low side of the system with the compressor operating Pre charging on the high side and adding liquid on the low side of the system are both meant to protect the compressor from operating with abnormally low suction pressures during charging NOTICE Do not operate the compressor without enough system charge to maintain at least 55 psig 3 8 ba...

Страница 14: ...ng one side only it is very possible that either the high or low side of the system remains pressurized If a brazing torch is then used to disconnect tubing the pressurized refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame Instructions should be provided in appropriate product literature and assembly line repair areas If compressor removal is required the comp...

Страница 15: ...ecommendations NOTICE It is highly recommended that the suction accumulator be replaced if the system contains one This is because the accumulator oil return orifice or screen may be plugged with debris or may become plugged shortly after a compressor failure This will result in starvation of oil to the replacement compressor and a second failure The system contactor should be inspected for pitted...

Страница 16: ... ng Temperature C Condensing Temperature C Condensing Temperature F Evapora ng Temperature F 29 19 9 1 11 21 31 4 14 24 34 44 54 64 40 50 60 70 80 90 100 110 120 130 140 150 160 20 10 0 10 20 30 40 50 60 70 80 90 Evaporating Temperature C Condensing Temperature C Condensing Temperature F Evaporating Temperature F ZP KW Pool Envelope ZP K3 ZP KC Envelope Figure 1a Operating Envelope Figure 1b Opera...

Страница 17: ...mpressor Sump Temperature F Evaporating Temperature F 200 F 93 3 C Max Oil Temp Acceptable Unacceptable Too Much Refrigerant Dilu on See Note 1 Note 1 Operation in this refrigerant dilution area is safe in air to air heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Figure 2 ...

Страница 18: ... Label Figure 4 Crankcase Heater Connect the heater so that the connection point straddles the compressor seam weld ZP50 57K3 ZP61 143KC ZP70 83KW Seam Weld WARNING Verify the correct crankcase heater voltage for the application and ensure heater is properly grounded ...

Страница 19: ...e Discharge Manifold Assembly Suction Manifold Assembly Mounting Rail 2 Required Compressor to Rail Mounting Kit Tandem to Unit Mounting Kit Figure 5 Typical ZP KC Tandem 12 Min Tilt the Compressor a Minimum of 12 for Installation of the Oil Equalization Line Oil Equalization Line Figure 6 Tilted Tandem ...

Страница 20: ...evenly Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result Field Service WARNING Remove refrigerant ...

Страница 21: ...21 2015 Emerson Climate Technologies Inc AE4 1365 R4 Figure 8 ...

Страница 22: ...fler Not required Alternate Configuration Component Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Mass Suction muffler May be required Acts as dampening mass Table 2 Design Configurations Table 3 Compressor Refrigerant Charge Limits Model Frame Size Charge Limit 120 x Limit Tandem Charge Limit Pounds kg Pounds kg Pounds kg ZP50 57K3 ZP70 83KW...

Страница 23: ...case Heater 277V 70W 018 0095 09 21 Leads Crankcase Heater Junction Box 998 7024 00 All Models Terminal Cover 005 1213 00 ZP50 57K3 ZP61 91KC ZP70 83KW Terminal Cover Gasket 020 0964 00 Terminal Cover 005 1494 00 ZP104 143KC Terminal Cover Gasket 020 1390 00 Terminal Block 021 0227 03 ZP104 143KC All Voltages Terminal Block 021 0234 00 ZP50 57K3 ZP61 91KC ZP70 83KW 230 Volt Only Terminal Block 021...

Страница 24: ...1 1 Phase Only Comfort Alert Module 543 0038 02 All Models 3 Phase Only Discharge Line Thermostat 998 7022 02 ZP50 57K3 ZP61 83KC Fits 1 2 Tube Discharge Line Thermostat not available ZP91KC Fits 3 4 Tube Discharge Line Thermostat 998 0071 02 ZP104 143KC Fits 7 8 Tube Discharge Rotalock Pipe Plug 036 0008 16 ZP104 143KC 1 8 27 NPTF Discharge Rotalock O Ring Seal 028 0028 00 ZP50 57K3 ZP61 83KC Dis...

Страница 25: ...required per tandem Includes bolts washers and steel spacers Tandem Mounting Kit Rails To Unit 527 0150 00 ZPT100 114K3 ZPT122 182KC Includes sleeves washers and grommets 35 45 durometer Tandem Mounting Kit Rails To Unit 527 0177 00 ZPT208 286KC Includes sleeves washers and grommets 65 75 durometer Tandem Rail 074 1235 00 ZPT100 114K3 ZPT122 182KC 2 rails required per tandem Tandem Rail 574 0053 0...

Отзывы: