Single-Compressor Module
Installation
2.6 Electrical Controls
2.6.1 General Considerations
All shutdown devices are dry contact switches rated Class I, Division II that are wired to a terminal box
for connection to the packager supplied control circuit. The common wires on all switches are connected
together. All switches are closed unless a fault condition is detected.
All safety and protective devices must be installed and used in accordance with applicable codes and
regulations.
Switches
All switch connections are wired to terminal strips in a junction box on the Compressor Module.
Switch
Status
• Low Inlet Gas Pressure
Normally Open, closes on pressure rise
• High Discharge Gas Pressure
Normally Closed, opens on pressure rise
• High Temperature
Normally Closed, opens on temperature rise
Electrical Considerations - Variable Speed Compressor Module
• Compressor power for a variable speed Compressor Module is the
Variable Frequency Drive (VFD)
.
• Compressor speed control can be either a 4-20 mA or 0-10V signal (transducer supplied by customer)
applied to the VFD. Speed can also be manually controlled with a potentiometer or the VFD can be
set for a fixed speed.
• The Compressor is protected by the VFD.
• The customer control circuit must supply an
Enable
signal to the VFD before the drive will accept a
Run Fwd
signal.
• The VFD will start when the
Enable
signal is on and a
Run Fwd
signal is applied.
• The VFD will stop if the
Run Fwd
signal is off or the
Enable
signal is removed.
NOTE
The drive provides 24V for the
Enable
and
Run Fwd
signals.
The installer must connect the
Enable
and
Run Forward
terminals to the drive’s 24V terminal.