Code
Description
Cause
Action
Reset
L51
Cold-start lockout alarm
Number of cold-start
alarms due to suction
pressure exceeds
parameter D34 setting
or number of cold start
alarms due to
discharge line
temperature exceeds
parameter D33 setting
Digital compressor turns off and is
locked out
Hold "start" button for 5 sec or manual power off
and on
E52
Liquid watch
Digital input for liquid
receiver level open
Warning signal only
Check the gas charge; check for leaks
E53
Digital compressor down
Digital input for digital
compressor open and
digital compressor
active
Warning signal only
Check compressor protection
E54
Fixed compressor down
Digital input for fixed
compressor open and
compressor active
Warning signal only
Check compressor protection
E55
Fan f ailure
Fan alarm contact open Warning signal only
Check f ans protection
E60
Max pressure alarm of superheating Not used
E61
Min pressure alarm of superheating Not used
E62
High superheating alarm
Not used
E63
Low superheating alarm
Not used
E64
High room temperature alarm
Not used
E65
Low room temperature alarm
Not used
E66
Open door alarm
Not used
E80
rtC warning, date error
HW problem in the
board
Disable the rtC or change the board
0
E81
rtC warning, communication error
HW problem in the
board
Disable the rtC or change the board
0