44
AGL_Unit_LOCU_EN_Rev00
Code
Description
Cause
Action
Reset
L20
Lost phase lockout
Power supply phase
loss happened H12
times within one hour
(3-phase units)
The compressor will lock out
Hold "start" button for 5 sec or manual power off
and on
L21
Phase sequence lockout
Incorrect phase
sequence (3-phase
units)
The compressor will lock out
Manual power off and on
E22
Phase imbalance
One phase voltage
lower than H18
percentage of 3 phases
average voltage
(3-phase units)
The compressor is activated according
to H19
Automatically as soon as voltage is recovered
and H16 setting delay time-out
L22
Phase imbalance lockout
One phase voltage
lower than H18
percentage of 3 phases
average voltage
(3-phase units)
The compressor is activated according
to H19 = 1: OFF the unit
Manual reset: voltage recover and H16 setting
delay time-out
E23
Overcurrent compressor # 1
Electrical current higher
than H09 setting
The compressor will trip
Automatically: H08 delay time-out
L23
Overcurrent lockout compressor # 1
Overcurrent happened
H11 times within one
hour
The compressor will lock out (if H11
equal to 0, no compressor lockout)
Hold "start" button for 5 sec or manual power off
and on (if H11 equal to 0, compressor starts
automatically after H08 delay time-out)
E24
Open run circuit error
Not used
L24
Open run circuit lockout
Not used
E25
Open start circuit error
Not used
L25
Open start circuit lockout
Not used
E26
Undervoltage alarm
Voltage lower than H13
setting for H15 seconds
The compressor will trip
Automatically as soon as voltage is back within
acceptable range and H16 delay time-out
L26
Undervoltage lockout
Undervoltage
happened H17 times
within one hour
The compressor will lock out (if H17
equal to 0, no compressor lockout)
Hold "start" button for 5 sec or manual power off
and on (if H17 equal to 0, compressor starts
automatically when voltage is back within
acceptable range and H16 delay time-out)
E27
Overvoltage alarm
Voltage higher than
H14 setting for H15
seconds
The compressor will trip
Automatically as soon as voltage is back within
acceptable range and H16 delay time-out