16
AGL_Unit_LOCU_EN_Rev00
2.11 XCM25D Electronic controller
– Programming
CAUTION
Low refrigerant charge! Compressor damage!
Never energize the
unit/controller without minimum ref rigerant system charge. There is a risk of
malf unction of the controller in deep vacuum operation which can cause
compressor damage.
2.11.1 Programming the local display
Figure 16: Local display
LED
Mode
Function
On
Compressor 1 enabled
Flashing
Anti-short cycle delay enabled
On
Condensing fans enabled
On
Display in bar
Flashing
Programming mode
On
Display in PSI
Flashing
Programming mode
On
When browsing the service menu
Flashing
In fast access menu
On
When browsing the alarm menu
Flashing
A new alarm occurred
On
An alarm is occurring
On
Digital unloader solenoid On
Table 11: LED functions description
NOTE: By default, the local display will show the value of the suction pressure during
operation. This can be changed by choosing another value for parameter B03 (Remote
Display visualization).
Setting for
B03
Value shown on the display
Comments
0
P1 value = Suction pressure
1
P2 value = Condensing pressure
2
P3 value = Discharge line temperature
3
P4 value = nu
Not used
4
P5 value = nu
Not used
5
P6 value = Ambient temperature
6
P7 value = Rescue mode
7
PEr value = Probe error
8
Aou value = Analog output
Table 12: Display visualisation