Table 3-12. Jumper Assignments: UDI Module
Jumper Purpose
Description
W1 Configures
UDI1
Pins 1-2 installed = Enable Debounce (Factory
default
). A
change of state on
both
the SET and RST (reset) field
inputs is required to accumulate counts.
Pins 2-3 installed = Disable Debounce. A change of state
on the SET field input is required to accumulate counts.
W2 through
W6
Configures UDI 2 through UDI6
Pins 1-2 installed = Enable Debounce (Factory
default
). A
change of state on
both
the SET and RST (reset) field
inputs is required to accumulate counts.
Pins 2-3 installed = Disable Debounce. A change of state
on the SET field input is required to accumulate counts.
Wiring the Module
shows field wiring assignments for the locally terminated
UDI module. It also includes examples for relay contact and open
collector applications.
shows field wiring assignments for
the remotely terminated UDI module.
Figure 3-25. UDI (Debounce Enabled) Wiring Diagram
Figure 3-26. UDI (Debounce Disabled) Wiring Diagram
Revised Nov-2010
I/O Modules
3-31