![Emerson ControlWave Скачать руководство пользователя страница 143](http://html.mh-extra.com/html/emerson/controlwave/controlwave_instruction-manual_102109143.webp)
Redundant Power Supply Sequencer Module (RPSSM)
Figure P-8. – Location of TB2 on ControlWave I/O Switcher
Wiring Digital Inputs to indicate Power Supply Failure
Each power supply on the RPSSM drives a solid state relay contact
closed during normal operation. In a failure, this contact opens. You can
optionally wire the contact to a digital input (either externally or
internally sourced) to provide indication of a power supply failure. You
must wire the contact differently depending upon whether the digital
input supports internally sourced or externally sourced power. See
Table
P-2
for details.
Table P-2. Wiring a Digital Input to Indicate Power Supply Failure
Power Supply
Digital Input (Internally Sourced) Digital
Input
(Externally
Sourced)
1
TB3-1 SYSTEM GND
TB3-2 DIGITAL INPUT
TB3-1 SYSTEM PWR
TB3-2 DIGITAL INPUT
2
TB3-3 SYSTEM GND
TB3-4 DIGITAL INPUT
TB3-3 SYSTEM PWR
TB3-4 DIGITAL INPUT
Hot-swapping a Power Supply
WARNING
DO NOT ATTEMPT hot swapping in a Class I, Division 2 hazardous
location.
Each power supply has a Power Good indication LED (see
Figure P-10
).
If this light goes out while the power supply is on, the power supply’s
output voltage is out of specification. This could occur if the supply is not
properly seated in the slot or if its fuse has blown. Remove the power
supply to check for these conditions. If neither condition has occurred,
you may need to replace the power supply.