![Emerson ControlWave Скачать руководство пользователя страница 140](http://html.mh-extra.com/html/emerson/controlwave/controlwave_instruction-manual_102109140.webp)
Redundant Power Supply Sequencer Module (RPSSM)
Figure P-3. Jumper Locations
Make the necessary adjustments to the jumpers according to
Table P-1
.
When finished, re-attach the case by first aligning the protective case with
the screw holes, then inserting and tightening each screw.
Wiring Power Connections
Use terminal blocks TB1 and TB2 to connect an external bulk power
supply to the RPSSM. An external 24V power supply (22.2 to 30V)
connected to
TB1
provides system power to the ControlWave including
the CPU boards and I/O boards (see
Figure P-4
).
Note
:
Be sure you route wires to the terminal block connectors so they
do not interfere with removal/replacement of the power supply
modules.
Figure P-4. Wiring System Power to the RPSSM
An external power supply (22.2 to 30V) connected to
TB2
provides field
power to I/O boards, and any field devices (switches, relays, etc.)
powered through the I/O boards (see
Figure P-5
).
P-4
Installation and Use
Revised Nov-2010