background image

CWPAC 

 December 

2010 

Technical Specifications 

ControlWave

®

 PAC  

Process Automation Controller

The ControlWave

®

 PAC is a highly adaptable 

Process Automation Controller with exceptional 
networking capability. Designed with an emphasis 
on scalability and modularity, the ControlWave PAC 
can be configured to maximize the performance of a 
wide range of control systems. Emerson has 
developed this innovative controller to provide cost-
effective solutions by minimizing the time required 
for installation and configuration. 

Base Unit 

The ControlWave PAC base unit is constructed of a 
stainless steel housing that contains the CPU, 
power supply, and is available with a 4 or 8 I/O 
slots. These slots are used to add optional I/O 
modules.  

CPU Options 

The ControlWave PAC has a 100 MHz CPU module 
that contains 2 MB of SRAM, 64 MB of SDRAM, 
and 32 MB of flash memory. The CPU module is 
available with the following on-board communication 
port configurations:  

The ControlWave PAC combines the elements of a 
PLC and an RTU without compromising the unique 
features and capabilities of each device. The 
ControlWave PAC provides a modular architecture, 
expandable I/O capacity, and Ethernet networking 
capability that introduces the possibilities of open 
architecture for emerging communication standards 
and provides a simple solution for existing networks.  

ƒ

 

One Ethernet port and two RS-232 ports 

ƒ

 

One Ethernet port, three RS-232 ports, and one 
RS-485 port 

ƒ

 

Three Ethernet ports, three RS-232 ports, and 
one RS-485 port 

Features  

ƒ

 

Three Ethernet ports, two RS-232 ports, and 
two RS-485 ports 

ƒ

 

Powerful, high-performance processor 

ƒ

 

Up to three 10/100 MB Ethernet ports 

Power Modules 

ƒ

 

Up to four serial communication ports 

The power module is installed in the first slot of the 
ControlWave PAC base unit and provides power to 
the rest of the device. Two power modules are 
available including: 

ƒ

 

4- and 8-slot I/O base unit 

ƒ

 Hot-swappable 

I/O 

ƒ

 

Security key-lock  

ƒ

 

Analog outputs maintain last/preset value on 
CPU watchdog 

ƒ

 

24 volt input power supply sequencer module 

ƒ

 

24 volt redundant power supply sequencer 
module 

ƒ

 

Discrete outputs maintain last or zero value on 
CPU watchdog 

Open Network Connectivity 

ƒ

 

Wide temperature range (-40 to +70ºC) 

ƒ

 

Class I, Div. 2 hazardous location and CE 
approval 

Remote Automation Solutions 

Website:  www.EmersonProcess.com/Remote 

By embracing the open systems network 
technologies available through TCP/IP, Ethernet, 
OPC, and Microsoft DNA (as well as pseudo 
standards such as Modbus and Open Modbus) the 
ControlWave PAC provides a total process 
automation management solution for in-plant  
LAN-based and wide area network SCADA 
systems. Access to real-time data and operating 
conditions, historical data, maintenance, and 
performance data stored in the ControlWave PAC is 
available to the global network.  

ƒ

 

Open industry standards for programming, 
configuration, and communication 

 

D301303X012 

 

ControlWave PAC

 

Содержание Bristol ControlWave PAC

Страница 1: ...ne Ethernet port and two RS 232 ports One Ethernet port three RS 232 ports and one RS 485 port Three Ethernet ports three RS 232 ports and one RS 485 port Features Three Ethernet ports two RS 232 ports and two RS 485 ports Powerful high performance processor Up to three 10 100 MB Ethernet ports Power Modules Up to four serial communication ports The power module is installed in the first slot of t...

Страница 2: ...D module with 4 points Thermocouple TC module with 6 points UDI Counter module with 6 points Note Modules are hot swappable All I O is frozen for 300 milliseconds when any module is replaced Remote Termination Modules The remote termination option for the ControlWave PAC modules provides a convenient alternative to the standard direct connect termination All remote termination modules are standard...

Страница 3: ... reports If any data is missed due to a communication failure it is collected and the PC historical database is backfilled when the communication is reestablished This distributed historical database architecture provides data reliability and integrity during communication or PC failure Another important historical feature is the audit system The audit logs are files stored in ControlWave flash me...

Страница 4: ...controllers RTUs PLCs and flow computers through the OpenBSI Communications Interface ObjectServer supports serial multi drop remote telemetry and Ethernet communication networks Unlike traditional OPC servers ObjectServer provides reliable access to RTUs that are connected via low bandwidth high latency and poor quality networks such as radio satellite and cellular modems ControlWave PAC CPU Modu...

Страница 5: ... Voltage Input Isolated differential inputs 1 5 Vdc Current Input Externally sourced current loop with 1 5 V input module and 250 ohm resistor across the input terminals or 4 20 mA input module On board isolated loop power supply for internally powered AI Input Impedance 1 megOhm for 1 5 Vdc 250 Ohm for 4 20 mA Common Mode Rejection 70 db Normal Mode Rejection 26 db Input Filtering 300 millisecond...

Страница 6: ...acy 0 1 of span 25 C for current output 0 2 of span 20 to 70 C for current output 0 3 of span 40 to 70 C for current output Settling Time 1 millisecond Status Indicator FAIL and OK module status LED Surge Suppression 500 Vdc MOV isolated common to chassis 31 Vdc transorb across output signals and negative output to common Fail Safe Configurable Output Fail State hold last value zero 5 to specified...

Страница 7: ...r 32 Type Solid state open source MOSFET Connector Terminal block or remote termination Voltage Range 10 31 Vdc Maximum Operating Frequency 20 Hz Current Sink Load Capability 500 mA at 31 Vdc Electrical Isolation 1500 Vdc Surge Suppression 500 MOV to chassis 31 Vdc transorb between signal and isolated ground Status Indicator LED per point status and module OK FAIL LED Fail Safe Configurable as Fai...

Страница 8: ...puts Input Accuracy Varies by thermocouple type 0 025 of span at 25 C for 10 mV input 0 05 of span 25 C to 70 C for 10 mV input Common Mode Rejection 120 db Normal Mode Rejection 80 db Electrical Isolation 500 Vdc channel to channel and channel to bus Surge Suppression 180 Vdc transorb between signal and ground Status Indicator Normal Over Under Range and module OK FAIL LEDs Cold Junction Compensa...

Страница 9: ...dication Active Fail and Power OK Physical Dimensions 4 I O Slot Chassis Panel Mount 300 73 mm W by 177 03 mm H by 125 98 mm D 11 84 in W by 6 97 in H by 4 96 in D 8 I O Slot Chassis Panel Mount or 19 Inch Rack Mount 481 58 mm W by 177 03 mm H by 125 98 mm D 18 96 in W by 6 97 in H by 4 96 in D Weight 4 I O Slot Chassis 3 18 kg 7 lbs 8 I O Slot Chassis 5 9 kg 13 lbs Wiring Up to 14 American Wire G...

Страница 10: ...Emerson Electric Co The Emerson logo is a trademark and service mark of the Emerson Electric Co All other marks are property of their respective owners The contents of this publication are presented for informational purposes only While every effort has been made to ensure informational accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or s...

Отзывы: