Emerson Bristol ControlWave PAC Скачать руководство пользователя страница 2

CWPAC 

 Page 

Technical Specifications 

 

Communications  

The ControlWave PAC supports up to seven 
communication ports. The base CPU module has 
two RS-232 serial ports and one Ethernet port. Two 
additional RS-232 or RS-485 serial ports and two 
additional Ethernet ports are optional. 

Communication Protocols 

ControlWave PAC supports BSAP (Bristol Standard 
Asynchronous Protocol), Modbus, DF1, CIP, DNP3, 
and serial ASCII communication protocols as 
standard features. ControlWave PAC also supports 
the following Modbus protocols: 

ƒ

 

Modbus serial and TCP/IP Open Modbus 
(Ethernet) 

ƒ

 

Master and Slave 

ƒ

 

Modbus RTU and ASCII 

ƒ

 

Function Codes 1–7, 8, 15, and 16 

ƒ

 

Integer and IEEE 4-byte floating point  

ƒ

 Coils 

Inputs and Outputs 

Input and output (I/O) modules are designed to 
maximize usability while minimizing installation, 
maintenance, and system down-time costs. A pull-
down door provides front panel wiring terminal 
access for technicians. The bezel and the 
terminations can be easily removed from the I/O 
module to make wiring even easier. In addition, a 
wide range of applications is supported by the 
availability of both local terminations and remote 
DIN-rail terminations. 

To minimize field wiring and eliminate the need for 
marshalling strips, the analog input (AI) and discrete 
input (DI) modules are capable of supplying loop 
power to two-wire transmitters and dry contacts.  

Status indicators offer instant visual notification of 
I/O conditions. Each I/O module has a two-color 
Pass/Fail LED that displays the online diagnostic 
status. Discrete I/O modules provide status LEDs 
for each point on the module. AI modules provide 
two LEDs on each input point to indicate input 
under/over range conditions. 

The ControlWave PAC supports a wide variety of 
I/O modules. Available I/O modules include: 

ƒ

 

Analog Input (AI) module with 8 or 16 points 

ƒ

 

Analog Output (AO) module with 8 points 

ƒ

 

Discrete Input (DI) module with 16 or 32 points  

ƒ

 

Discrete Output (DO) module with 16 or 32 
points  

ƒ

 

Resistance Temperature Detector (RTD) 
module with 4 points 

ƒ

 

Thermocouple (TC) module with 6 points 

ƒ

 

UDI Counter module with 6 points 

Note:

  Modules are hot-swappable. All I/O is frozen 

for 300 milliseconds when any module is 
replaced. 

Remote Termination Modules 

The remote termination option for the ControlWave 
PAC modules provides a convenient alternative to 
the standard direct connect termination. All remote 
termination modules are standard DIN-rail 
mountable, and connect to the I/O module with pre-
wired connector cables. To simplify installation, all 
I/O modules use the same cable.  

I/O Expansion Rack 

The I/O Expansion Rack allows for the addition of 
I/O modules to multiple local and remote mounted 
racks. The I/O Expansion Rack consists of a 4- or 8-
slot ControlWave chassis. This chassis contains an 
Ethernet communication engine dedicated to 
communications between the main processor and 
the I/O Expansion Rack. The communication engine 
also supports battery backed RAM to retain output 
values during short power outages.  

The I/O Expansion Rack is connected to the main 
ControlWave via an Ethernet physical link using 
TCP/IP. The process control application program 
resides in the main ControlWave. The main 
ControlWave controls both local I/O as well as the 
I/O located in the I/O Expansion Rack.  

ControlWave Redundant Systems 

Redundant systems are ideal for use in critical 
processes and harsh applications that require 
maximum operational readiness and system 
availability. The ControlWave PAC redundant 
systems are designed to prevent a single point of 
failure from shutting down the entire system. Two 
types of redundant systems are available for the 
ControlWave PAC: the redundant process control 
and communications system, and the redundant 
input/output (I/O) system. For more information on 
the ControlWave PAC redundant systems, refer to 

Technical Specifications CWPAC:RDN

Key Switch 

The ControlWave PAC is available with a three-
position front panel key switch. The front panel key 
switch provides a high level of manual security by 
controlling three modes of operation. 

In Run Mode, the ControlWave PAC rejects any 
attempt to download or modify the running program, 
either locally or over the network. 

Содержание Bristol ControlWave PAC

Страница 1: ...ne Ethernet port and two RS 232 ports One Ethernet port three RS 232 ports and one RS 485 port Three Ethernet ports three RS 232 ports and one RS 485 port Features Three Ethernet ports two RS 232 ports and two RS 485 ports Powerful high performance processor Up to three 10 100 MB Ethernet ports Power Modules Up to four serial communication ports The power module is installed in the first slot of t...

Страница 2: ...D module with 4 points Thermocouple TC module with 6 points UDI Counter module with 6 points Note Modules are hot swappable All I O is frozen for 300 milliseconds when any module is replaced Remote Termination Modules The remote termination option for the ControlWave PAC modules provides a convenient alternative to the standard direct connect termination All remote termination modules are standard...

Страница 3: ... reports If any data is missed due to a communication failure it is collected and the PC historical database is backfilled when the communication is reestablished This distributed historical database architecture provides data reliability and integrity during communication or PC failure Another important historical feature is the audit system The audit logs are files stored in ControlWave flash me...

Страница 4: ...controllers RTUs PLCs and flow computers through the OpenBSI Communications Interface ObjectServer supports serial multi drop remote telemetry and Ethernet communication networks Unlike traditional OPC servers ObjectServer provides reliable access to RTUs that are connected via low bandwidth high latency and poor quality networks such as radio satellite and cellular modems ControlWave PAC CPU Modu...

Страница 5: ... Voltage Input Isolated differential inputs 1 5 Vdc Current Input Externally sourced current loop with 1 5 V input module and 250 ohm resistor across the input terminals or 4 20 mA input module On board isolated loop power supply for internally powered AI Input Impedance 1 megOhm for 1 5 Vdc 250 Ohm for 4 20 mA Common Mode Rejection 70 db Normal Mode Rejection 26 db Input Filtering 300 millisecond...

Страница 6: ...acy 0 1 of span 25 C for current output 0 2 of span 20 to 70 C for current output 0 3 of span 40 to 70 C for current output Settling Time 1 millisecond Status Indicator FAIL and OK module status LED Surge Suppression 500 Vdc MOV isolated common to chassis 31 Vdc transorb across output signals and negative output to common Fail Safe Configurable Output Fail State hold last value zero 5 to specified...

Страница 7: ...r 32 Type Solid state open source MOSFET Connector Terminal block or remote termination Voltage Range 10 31 Vdc Maximum Operating Frequency 20 Hz Current Sink Load Capability 500 mA at 31 Vdc Electrical Isolation 1500 Vdc Surge Suppression 500 MOV to chassis 31 Vdc transorb between signal and isolated ground Status Indicator LED per point status and module OK FAIL LED Fail Safe Configurable as Fai...

Страница 8: ...puts Input Accuracy Varies by thermocouple type 0 025 of span at 25 C for 10 mV input 0 05 of span 25 C to 70 C for 10 mV input Common Mode Rejection 120 db Normal Mode Rejection 80 db Electrical Isolation 500 Vdc channel to channel and channel to bus Surge Suppression 180 Vdc transorb between signal and ground Status Indicator Normal Over Under Range and module OK FAIL LEDs Cold Junction Compensa...

Страница 9: ...dication Active Fail and Power OK Physical Dimensions 4 I O Slot Chassis Panel Mount 300 73 mm W by 177 03 mm H by 125 98 mm D 11 84 in W by 6 97 in H by 4 96 in D 8 I O Slot Chassis Panel Mount or 19 Inch Rack Mount 481 58 mm W by 177 03 mm H by 125 98 mm D 18 96 in W by 6 97 in H by 4 96 in D Weight 4 I O Slot Chassis 3 18 kg 7 lbs 8 I O Slot Chassis 5 9 kg 13 lbs Wiring Up to 14 American Wire G...

Страница 10: ...Emerson Electric Co The Emerson logo is a trademark and service mark of the Emerson Electric Co All other marks are property of their respective owners The contents of this publication are presented for informational purposes only While every effort has been made to ensure informational accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or s...