CWPAC 

Technical Specifications 

 Page 

ACCOL III 

In addition to the basic functions and function 
blocks, ControlWave Designer brings the benefit of 
over twenty years of SCADA and plant control 
experience in Emerson’s ACCOL III function block 
library. ACCOL III includes over sixty function blocks 
valuable for use in oil and gas, water and waste, 
and process measurement and control applications. 
ACCOL III is designed to take full advantage of the 
significant features offered by ControlWave.  

The library consists of many function blocks 
including: 

ƒ

 

Average, Compare, Totalize 

ƒ

 

Scheduling and Sequencing 

ƒ

 

PID and Lead/Lag 

ƒ

 

AGA Gas Flow and Liquids Calculations 

ƒ

 File 

Handling 

ƒ

 NIST-23 

ObjectServer 

ObjectServer is an optional OPC-compliant server 
that provides direct communication to the 
ControlWave family of controllers, RTUs, PLCs, and 
flow computers through the OpenBSI 
Communications Interface. ObjectServer supports 
serial multi-drop, remote telemetry, and Ethernet 
communication networks. Unlike traditional OPC 
servers, ObjectServer provides reliable access to 
RTUs that are connected via low-bandwidth, high-
latency, and poor-quality networks such as radio, 
satellite, and cellular modems.

 

ControlWave PAC 

CPU Module 

Processor 

Type 

586 CPU, 100 MHz 

Memory Boot 

512 

kB 

 

Flash 

32 MB on-board 

 

SRAM 

2 MB, battery backed 

 

SDRAM 

64 MB (66MHz SDRAM coupled to a 32-bit bus) 

Clock 

Accuracy 

2 second/day at 25˚C 

Communications 

COM1 Type 

RS-232 

 

Connector 

PC/AT 9-pin male D-sub 

 

Baud 

Up to 115.2 KB 

COM2 Type 

RS-232 

 

Connector 

PC/AT 9-pin male D-sub 

 

Baud 

Up to 115.2 KB 

COM3 (optional) 

Type 

RS 232 or RS 485 

 Connector 

RJ45 

 

 

Baud 

Up to 115.2 KB 

 

Isolation 

500 Vdc (RS-485 only) 

COM4 (optional) 

Type 

RS-485 

 

Connector 

PC/AT 9-pin male D-sub 

 Isolation 

500 

Vdc 

Ethernet Port 1 

Type 

10/100 Base-T Ethernet port 

 Connector 

RJ45 

 Isolation 

500 

Vdc 

Содержание Bristol ControlWave PAC

Страница 1: ...ne Ethernet port and two RS 232 ports One Ethernet port three RS 232 ports and one RS 485 port Three Ethernet ports three RS 232 ports and one RS 485 port Features Three Ethernet ports two RS 232 ports and two RS 485 ports Powerful high performance processor Up to three 10 100 MB Ethernet ports Power Modules Up to four serial communication ports The power module is installed in the first slot of t...

Страница 2: ...D module with 4 points Thermocouple TC module with 6 points UDI Counter module with 6 points Note Modules are hot swappable All I O is frozen for 300 milliseconds when any module is replaced Remote Termination Modules The remote termination option for the ControlWave PAC modules provides a convenient alternative to the standard direct connect termination All remote termination modules are standard...

Страница 3: ... reports If any data is missed due to a communication failure it is collected and the PC historical database is backfilled when the communication is reestablished This distributed historical database architecture provides data reliability and integrity during communication or PC failure Another important historical feature is the audit system The audit logs are files stored in ControlWave flash me...

Страница 4: ...controllers RTUs PLCs and flow computers through the OpenBSI Communications Interface ObjectServer supports serial multi drop remote telemetry and Ethernet communication networks Unlike traditional OPC servers ObjectServer provides reliable access to RTUs that are connected via low bandwidth high latency and poor quality networks such as radio satellite and cellular modems ControlWave PAC CPU Modu...

Страница 5: ... Voltage Input Isolated differential inputs 1 5 Vdc Current Input Externally sourced current loop with 1 5 V input module and 250 ohm resistor across the input terminals or 4 20 mA input module On board isolated loop power supply for internally powered AI Input Impedance 1 megOhm for 1 5 Vdc 250 Ohm for 4 20 mA Common Mode Rejection 70 db Normal Mode Rejection 26 db Input Filtering 300 millisecond...

Страница 6: ...acy 0 1 of span 25 C for current output 0 2 of span 20 to 70 C for current output 0 3 of span 40 to 70 C for current output Settling Time 1 millisecond Status Indicator FAIL and OK module status LED Surge Suppression 500 Vdc MOV isolated common to chassis 31 Vdc transorb across output signals and negative output to common Fail Safe Configurable Output Fail State hold last value zero 5 to specified...

Страница 7: ...r 32 Type Solid state open source MOSFET Connector Terminal block or remote termination Voltage Range 10 31 Vdc Maximum Operating Frequency 20 Hz Current Sink Load Capability 500 mA at 31 Vdc Electrical Isolation 1500 Vdc Surge Suppression 500 MOV to chassis 31 Vdc transorb between signal and isolated ground Status Indicator LED per point status and module OK FAIL LED Fail Safe Configurable as Fai...

Страница 8: ...puts Input Accuracy Varies by thermocouple type 0 025 of span at 25 C for 10 mV input 0 05 of span 25 C to 70 C for 10 mV input Common Mode Rejection 120 db Normal Mode Rejection 80 db Electrical Isolation 500 Vdc channel to channel and channel to bus Surge Suppression 180 Vdc transorb between signal and ground Status Indicator Normal Over Under Range and module OK FAIL LEDs Cold Junction Compensa...

Страница 9: ...dication Active Fail and Power OK Physical Dimensions 4 I O Slot Chassis Panel Mount 300 73 mm W by 177 03 mm H by 125 98 mm D 11 84 in W by 6 97 in H by 4 96 in D 8 I O Slot Chassis Panel Mount or 19 Inch Rack Mount 481 58 mm W by 177 03 mm H by 125 98 mm D 18 96 in W by 6 97 in H by 4 96 in D Weight 4 I O Slot Chassis 3 18 kg 7 lbs 8 I O Slot Chassis 5 9 kg 13 lbs Wiring Up to 14 American Wire G...

Страница 10: ...Emerson Electric Co The Emerson logo is a trademark and service mark of the Emerson Electric Co All other marks are property of their respective owners The contents of this publication are presented for informational purposes only While every effort has been made to ensure informational accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or s...