background image

Product Data Document

420DS-4c

July 19, 2007 - Page 2

Bristol

®

 ControlWave

®

 LP

Remote Automation Solutions

Website:  www.EmersonProcess.com/Remote

Fused with power-on switch.
Master Clear and Power Fail Indication
Power sequencer for auto power recovery
Power supply isolation:  500 VDC 
Surge Suppression:  500 VDC MOV PSGND 

to CHASSIS

 

32 V Transient suppressor across 

VIN + to PSGND Meets ANSI/IEEE C37.90-

1978

Low Power Mode

ControlWave LP power consumption is highly 

dependent on the actual application program and 

whether or not you are using internal loop power to 

field devices. 

Typical power consumption range: 150 to 200 mA 

@ 24 Vdc  

Fixed Multifunction Input/Output Board

The Fixed Multifunction Input/Output Board (FMI/

OB) contains four I/O modules with pluggable termi-

nations and a PC-104 Interface for interconnection 

of fixed and expansion I/O subsystems.  The board 

also provides for electrical isolation to field devices, 

surge suppression, and LED indicators for Discrete 

I/O, CPU, and communications functions.  The four 

I/O modules are fixed as follows:

16 Discrete Inputs
8 Discrete Outputs
4 High Speed Counters
8 Analog Inputs

Two on-board Field Power Supplies are provided: 

one for DI and HSC operation and one for AI opera-

tion. The output voltages are electrically isolated 

(500 VDC) and are regulated at 24V.








Specifications

CPU

Intel Ultra Low Power 486SX 32 bit processor 

-25 MHz
Data Storage Memory:  2 MB SRAM battery 

backed memory
Historical Archive Memory:  Stored in either 

flash or battery backed SRAM

Code/ Instruction Memory:  4 MB on-board 

FLASH
BIOS:  512 Kbytes Boot-Block FLASH

Communication

Four RS-232 serial communication ports with 

standard PC/AT 9-pin male D-sub connectors, 

supporting baud rates up to 115.2 KB
One selectable RS 232 or RS 485 serial 

communication port with standard PC/AT 9-pin 

male D-sub connector, supporting baud rates up 

to 115.2 KB
RS 485 port has line pull-ups and termination 

resistor
Modem control on all ports.
One 10 Base-T Ethernet port with RJ45 

connector - Optional.
Isolation: Ethernet port isolated to 500 Vdc

Power Supply/Sequencer Board

Input Power:  12 or 24 VDC input: 10 to 22 VDC 

or 22 to 30 VDC
Plugs into Multifunction Motherboard
Provides system is 5 VDC & +/- 12 VDC 

power



Содержание Bristol ControlWave LP

Страница 1: ...the ControlWave and Network 3000 family of process automation controllers and RTU s The ControlWave LP is compact in size and offers the full programmabil ity of ControlWave Designer IEC 61131 compliant software and communicates via standard BSAP as well as other industry standard protocols The ControlWave LP is available in an open chassis assembly for mounting to a panel or within an enclo sure ...

Страница 2: ...he four I O modules are fixed as follows 16 Discrete Inputs 8 Discrete Outputs 4 High Speed Counters 8 Analog Inputs Two on board Field Power Supplies are provided one for DI and HSC operation and one for AI opera tion The output voltages are electrically isolated 500 VDC and are regulated at 24V Specifications CPU Intel Ultra Low Power 486SX 32 bit processor 25 MHz Data Storage Memory 2 MB SRAM b...

Страница 3: ...o chassis 38 VDC MOV across input signals and input to chassis Meets ANSI IEEE C37 90 1978 Terminations Pluggable maximum wire size is 16 gauge Bus Access 16 Bits Wide ControlWave LP Analog Input Module Number of Points 8 Input Configuration Isolated Voltage Input 1 5V Isolated Current Input 4 20 mA Powered Current Loop 4 20 mA Accuracy 0 1 of span 25 deg C 0 2 of span 20 deg C to 70 deg C 0 3 of ...

Страница 4: ... Accuracy 0 1 of span 25o C 0 2 of span 20 to 70 o C 0 3 of span 40 to 85 o C Common Mode Voltage 500 VDC AO ground to chassis Surge Suppression 16 V Transorb across input to AO Ground Meets ANSI IEEE C37 90 1975 Environmental Specifications Operating Temperature 40o C to 70o C 40o F to 158o F Storage Temperature 40o C to 85o C 40o F to 185o F Relative Humidity 15 95 Noncondensing Vibration 10 150...

Страница 5: ...al OPC Server HistTools Historical Data Collector Scheduler and File Converter By adhering to such industry standards as Ethernet TCP IP Microsoft Windows COM DCOM OLE and Active X ControlWave is able to achieve the highest degree of openness in control system architecture and bring you the optimal process efficiency and productivity you need to ensure a successful system implementation To minimiz...

Страница 6: ...utilities to easily create the OPC server database from the ControlWave application configuration files then provide access to those variables to any OPC compliant HMI product for operator display and interaction with the ControlWave network HistTools Historical collection and storage Communication engine for PC applications Supports ControlWave and Network 3000 serial and IP protocols RS 232 Dial...

Страница 7: ... Technicians Toolkit are WebBSI A set of Active X controls allowing commu nication access to ControlWave are provided for en gineers to develop their own custom web pages us ing any standard package such as Microsoft Front Page Active X controls allow data to be viewed in any compliant container such as Microsoft Excel and Word or Visual Basic or a compliant web page Browser such as Microsoft Inte...

Страница 8: ...ature is the Audit storage and collection system The audit trail is a file stored in ControlWave Flash memory containing significant events and time stamped alarms The alarms stored in the Audit system provide a histori cal archive in addition to the real time alarm report ing system This file is also collected through Open BSI and presented as a text file in the PC This Archive Collection collect...

Страница 9: ...leRTU ControlWave DPC 3335 Operator and Engineering Workstations WAN Plant Automation Management Solution Engineer Customer Serial Modbus ControlWave BSAP Modbus ControlWave Open Network Connectivity By embracing the open system network technolo gies available through TCP IP Ethernet OPC and Microsoft DNA as well as pseudo standards such as Modbus and Open Modbus ControlWave can provide a total Pr...

Страница 10: ... Audit file transfer On line program editing Diagnostics Communication statistics Modbus Modbus is often considered a de facto standard protocol because broad usage as ei ther the primary or a secondary offering in many measurement and control related products Even with its common use Modbus protocol actually has many variations Consider Modbus RTU and Modbus ASCII Master Slave Serial and TCP IP O...

Страница 11: ...ad the ControlWave The Secure Data Advantage ControlWave sets a new standard for providing in telligent control at the point where control is needed Whether you need control on the plant floor or at a remote site in the middle of nowhere ControlWave is the solution for control communication and secure data to help you make the right operating decisions ControlWave was designed to provide the optim...

Отзывы: