![Emerson Bristol ControlWave Express Скачать руководство пользователя страница 71](http://html.mh-extra.com/html/emerson/bristol-controlwave-express/bristol-controlwave-express_instruction-manual_101199071.webp)
ControlWave Express Instruction Manual (CI-ControlWave Express)
LED6
STA6
LED5
STA5
LED4
STA4
LED3
STA3
LED2
STA2
LED1
STA1
Status
In Hex
LCD
Display
Indication
Definition
0
0
1
0
1
1
0B
INIT
System Initialization in Progress
0
1
0
0
0
0
10
RECOV
Waiting in Recovery Mode
0
1
0
0
1
0
12
RAMERR
Error Testing SRAM
1 0 0 0 0 0 20
STOP Application
Loaded
1
0
1
0
0
0
28
HALT
Stopped at a Break Point
1
1
0
0
0
0
30
NO APP
No Application Loaded
1
1
1
0
0
0
38
BREAKP
Running with Break Points
1
1
1
0
1
1
3B
POWERD
Waiting for Power-down (after
NMI)
1
1
1
1
1
0
3E
UPDUMP
Waiting for Updump to be
Performed
1
1
1
1
1
1
3F
NOTRUN
Unit Crashed (Watchdog
Disabled)
In addition to the LEDs on the piggy-back LED board, the CPU/System
Controller board includes a watchdog LED (WD – CR1 right) and an
idle LED (IDLE – CR1 left) that have identical functions to WD and
IDLE described in
Table 5-1
.
Revised Mar-2011
Service & Troubleshooting
5-11
WD LED
IDLE LED
Figure 5-8. WD and IDLE LEDs
Содержание Bristol ControlWave Express
Страница 4: ...This page is intentionally left blank ...
Страница 38: ...This page is intentionally left blank ...
Страница 54: ...This page is intentionally left blank ...
Страница 78: ...This page is intentionally left blank ...
Страница 82: ...This page is intentionally left blank ...
Страница 84: ...This page is intentionally left blank ...