ControlWave Express Instruction Manual (CI-ControlWave Express)
1.
Connect a null modem cable between COM1 of the
ControlWave Express and any RS-232 port on the associated
PC.
2.
Click
Start
>
Programs
>
Accessories
>
Communications
>
HyperTerminal
3.
If using HyperTerminal for the first time, set the communication
properties (for the PC port) via the Properties Menu as follows:
Bits per second: = 115200, Data bits: = 8, Parity: = None, Stop
bits: = 1, and Flow control: = None and then click
OK
.
4.
Set CPU/System Controller board switch SW1-3
ON
(ON =
Force Recovery).
5.
Apply power; to the ControlWave Express. The resident BIOS
initializes and tests the hardware, this process is referred to as
POST (Power On Self Test). Unless there is a problem, status
LEDS show status code 10 (LED #5 ON). If you see a different
status code, see
Section 5.3.1.
6.
From the HyperTerminal Mode menu (
Figure 5-1
), press the
F
key to enter FLASH download. A message warns that the
FLASH is about to be erased; press the
Y
key at the prompt. The
screen displays dots as the system erases the flash memory; this
could take a few minutes.
Figure 5-1. HyperTerminal Mode Menu
7.
When the FLASH is ready for download, HyperTerminal
repeatedly displays the letter C on the screen. In the
HyperTerminal menu bar click
Transfer > Send File
(see
Figure 5-2
).
Revised Mar-2011
Service & Troubleshooting
5-3
Содержание Bristol ControlWave Express
Страница 4: ...This page is intentionally left blank ...
Страница 38: ...This page is intentionally left blank ...
Страница 54: ...This page is intentionally left blank ...
Страница 78: ...This page is intentionally left blank ...
Страница 82: ...This page is intentionally left blank ...
Страница 84: ...This page is intentionally left blank ...