Installation, Operation and Maintenance Manual
MAN-02-10-93-0700-EN Rev. 0
May 2019
31
Section 9: Remote Network Control
Remote Network Control
9.4
DeviceNet
The MPA uses CAM09 to convert between Modbus and DeviceNet. This section describes
the data mapping between the DeviceNet host and MPA Modbus map. The mapping allows
the DeviceNet host to control the Flow Selector and monitor actuator status.
The control information is mapped directly to words in the DeviceNet Output data and
status information are mapped directly to words in the DeviceNet Input data.
Table 13.
Output Data
Location
Bit
Word Byte
7
6
5
4
3
2
1
0
1
1
Not used
Host ESD
Com-
mand
Go to
Next
Point
Not used
2
Not used
2
3
Flow Selector Port Position Setpoint (0-7) Single Bit
4
3
5
Not used
6
Table 14.
Input Data
Location
Bit
Word Byte
7
6
5
4
3
2
1
0
1
0
Not used
Not used Not used Not used Not used Not used Not used
1
Not used Not used Not used Not used
Not used
2
2
Stopped
Between
Ports
Over
Torque
Alarm
Selector
Remote /
Auto
Selector
Local /
Manual
Wrong
Direction
Alarm
Flow
Selector
Moving
Within 2
Degrees
of port
Within 1
Degree of
port
3
Unit
Alarm
Not used
Actuator
Fail Alarm
Local ESD
Alarm
Phase
Monitor
Alarm
Motor
Thermal
Alarm
Power
Monitor
Alarm
Flow
Selector
Stall
Alarm
3
4
Flow Selector Position (0-7) Single Bit
5
4
6
Torque (0-99%)
7
5
8
Not used
9
6
10
Not used
11