Installation, Operation and Maintenance Manual
MAN-02-10-93-0700-EN Rev. 0
May 2019
Section 9: Remote Network Control
Remote Network Control
9.2
Foundation Fieldbus (FF)
The MPA uses a CAM18 to convert between Modbus and Foundation Fieldbus. Refer to
M2CP CAM18 & TEC2000 CAM218 Installation, Operation and Instruction Manual for
installation and setup of the FF link. Relations between the Modbus and FF maps are
identified as follows:
Foundation Fieldbus
Modubus Discrete Input
Map
Actuator Readback (Channel 2)
Note: Channel 2 has only 1 value
Input
DI
PV / Out_D
16
At port within 1 degree
1
17
At port within 1 degree
2
18
Flow selector moving
4
19
Wrong direction alarm
5
Modubus Discrete Input Map
Actuator Status (Channel 5)
Note: Channel 5 has only 1 discrete value and depends upon Selector Switch position.
DI
PV / Out_D
Input
AUTO
OFF
LOCAL
20
SS Local/Manual
3
Selector Switch Off
2
21
SS Remote/Auto
0
22
Over torque alarm
60
62
63
23
Stop between ports alarm
56
58
59
24
Flow selector stall alarm
9
11
12
25
Power monitor alarm
28
30
31
26
Motor thermal overload alarm
20
22
23
27
Phase monitor alarm
36
38
39
28
Local ESD alarm
40
42
43
29
Actuator fail alarm
44
46
47
Coil Map (Discrete Network Control)
Actuator Command (Channel 1)
Coil
DO
SP / Out_D
10
Go to Next Port
1
Coil Map (Discrete Network Control)
ESD Command (Channel 10)
Coil
DO
SP / Out_D
11
Host ESD Command
1
Monitor and Control Registers
Analog input / Output Channels
Register
11
Port Position Setpoint (0-7 or 1-8)
Setpoint AO (Channel 3)
SP / OUT
14
Port position (0-4095)
Position AI (Channel 4)
SP / OUT
15
Torque (0-99%)
Torque AI (Channel 18)
SP / OUT