9
Section 5: Local Display Module
Local Display Module
5.2
Operation
Place the “Selector Knob” in the desired operating position.
1.
LOCAL – hands on operation at the actuator by manipulation of Control Knob.
2.
REMOTE – used within the context of plant operation, i.e. Remote Control Panel,
PLC, DCS, etc. See wiring diagram for typical user wiring for remote control.
3.
OFF (Stop) – to prevent local or remote operation.
Figure 7
5.3
Local Operation
Place the “Selector Knob” in the “Local” position. If a remote display is connected, the
remote selector switch must not be in the “Off” position. Verify that the selector “L” amber
light is on. The actuator may now be operated using the port and jog Control Knobs. Jog
control is normally disabled and must be enabled in the setup menu.
To jog or micro-step the actuator toward the next port, rotate the control knob in the
counterclockwise direction. Jog to position and release when the desired position is
reached. When using jog for calibrating the actuator, always stop short of the desired port
and use the hand wheel to complete accurate positioning to center of the port.
To move only to the next port, momentarily rotate the control knob in the clockwise direc-
tion to the Port position and release.