Fault Insertion
In the unlikely event of a fault developing, the following Fault Location Table is provided to
assist the service engineer. This table is designed to cover a wide a range of Emerson Bettis
actuators as possible. Reference to equipment not supplied should be ignored.
Table 5�
Symptoms and Solutions Table
SYMPTOM
POTENTIAL CAUSES
REMEDY
Erratic movement
Irregular supply of operating
medium
Check operating medium for consistent
supply pressure and correct as
necessary
Inadequate lubrication
Dismantle, relubricate and reassemble
Worn parts
Dismantle and visually inspect
for significant wear and actuator
replacement may be required
Defective valve
Consult the valve OEM's documentation
Short stroke
Incorrectly set stops
(valve and/or actuator)
Check the position of the travel stops
and readjust as necessary
Hardened grease
Dismantle, remove any hard grease,
relubricate and reassemble
Debris left in the cylinder or
housing during maintenance
Disassemble cylinder assembly to
remove debris and reassemble cylinder
assembly as necessary
Defective valve
Consult the valve OEM documentation
Apparent lack of torque
Inadequate supply pressure
Ensure supply pressure is above the
minimum operating pressure of the
actuator and that output torque
produced at supply pressure exceeds
valve
torque demand
Incorrect speed control settings Adjust speed controls to increase flow
Exhaust port blocked
Remove and clean the exhaust port
silencers and replace
Pipe work blocked, crushed
or leaking
Examine the pipe work for blockages,
crushed pipe or leakage and clear or
replace
as necessary
Defective controls
Examine the controls, refurbish
or renew as necessary and refer
to component manufacturer's
documentation
Defective piston seal
Dismantle the cylinder assembly,
remove the defective piston seal and fit
new seal
and reassemble
Defective rod seal
Dismantle the cylinder assembly,
remove the defective rod seal and fit
new seal and reassemble
Defective housing seal
Dismantle the housing assembly,
remove the defective seal and fit new
seal and reassemble
High valve torque or valve seized Consult the valve OEM documentation