Observe the following general safety notes when installing your system:
z
Restricted access area - The system is only to be installed in a restricted access area.
z
Installation codes - This unit must be installed in accordance with the National Electrical
Code, Articles 110.16, 110.17, and 110.18 and the Canadian Electrical Code, Section 12.
z
Conductor ampacity - According to UL 60950, Annex NAE (NEC Article 645-5(a)), the
branch-circuit conductors supply must have an ampacity of not less than 125% of the
total connected load. Per NEC Article 310.15 and Table 310.16, the minimum American
Wire Gauge (AWG) has to be selected.
z
Overcurrent protection - A readily accessible listed branch-circuit overcurrent protective
device must be incorporated into the building wiring.
Emerson is not responsible for regulatory compliance or malfunction of any user-modified
product.
System Damage
Environmental contamination can impair system operation.
Locate the system in a stable area free of movement and free of dust, smoke, and
electrostatic discharge (ESD). Make sure, that the temperature does not exceed the
operating temperature given in the environmental requirements in this manual and allow
room for proper air cooling.
System Overheating
Improper cooling leads to blade damage.
To ensure proper cooling always operate the system in a horizontal position. Furthermore,
keep clear at least 6 cm adjacent to the cooling vents on the chassis front and back side.
Содержание AXP 1410
Страница 12: ...AXP 1410 Installation and Use 6806800H70F 12 List of Tables ...
Страница 14: ...AXP 1410 Installation and Use 6806800H70F 14 List of Figures ...
Страница 22: ...AXP 1410 Installation and Use 6806800H70F About this Manual 22 About this Manual ...
Страница 25: ...System Overview AXP 1410 Installation and Use 6806800H70F 25 Figure 1 2 System Rear View ...
Страница 62: ...System Installation AXP 1410 Installation and Use 6806800H70F 62 ...
Страница 82: ...FRU Installation AXP 1410 Installation and Use 6806800H70F 82 ...
Страница 118: ...Supported IPMI Commands AXP 1410 Installation and Use 6806800H70F 118 ...
Страница 164: ...FRU Information and Sensor Data Records AXP 1410 Installation and Use 6806800H70F 164 ...
Страница 201: ...Index AXP 1410 Installation and Use 6806800H70F 201 ...
Страница 202: ...Index AXP 1410 Installation and Use 6806800H70F 202 ...
Страница 203: ......