Site Preparation
AXP 1410 Installation and Use (6806800H70F)
39
2.3
Requirements
Before and during system installation and operation, you always have to ensure that the
requirements listed in the following sections are met.
2.3.1
Environmental Requirements
To ensure proper function of the system, make sure that the environment in which the system
is to be used fulfills the environmental requirements.
The environmental values must be tested and proven in the planned system configuration, that
means the delivered system and other third-party products you want to integrate.
The following table lists the environmental requirements.
Operating temperatures refer to the temperature of the air circulating at the air intake of the
system and not to component temperatures.
Some of the climatic values may exceed the specification of some system components (for
example hard disks). As Emerson cannot guarantee the functionality of third party products
that are handled or operated out of their specifications, the environmental conditions may be
limited to the specifications of these components.
Table 2-1 Environmental Conditions
Feature
Operating
Non-Operating (packed state)
Temperature
+5ºC (41°F) to +40ºC (104°F) (normal
operation)
according to NEBS standard GR-63-CORE
-5°C (23°F) to +55°C (131°F) (exceptional
operation)
according to NEBS standard GR-63-CORE
-40°C (-40°F) to +70°C (158°F)
Temp.
change
+/-0.25°C/min
according to NEBS standard GR-63-CORE
+/-0.25°C/min
Relative
humidity
5% to 90% non-condensing
according to Emerson-internal
environmental requirements
5% to 95% non-condensing
according to Emerson-internal
environmental requirements
Содержание AXP 1410
Страница 12: ...AXP 1410 Installation and Use 6806800H70F 12 List of Tables ...
Страница 14: ...AXP 1410 Installation and Use 6806800H70F 14 List of Figures ...
Страница 22: ...AXP 1410 Installation and Use 6806800H70F About this Manual 22 About this Manual ...
Страница 25: ...System Overview AXP 1410 Installation and Use 6806800H70F 25 Figure 1 2 System Rear View ...
Страница 62: ...System Installation AXP 1410 Installation and Use 6806800H70F 62 ...
Страница 82: ...FRU Installation AXP 1410 Installation and Use 6806800H70F 82 ...
Страница 118: ...Supported IPMI Commands AXP 1410 Installation and Use 6806800H70F 118 ...
Страница 164: ...FRU Information and Sensor Data Records AXP 1410 Installation and Use 6806800H70F 164 ...
Страница 201: ...Index AXP 1410 Installation and Use 6806800H70F 201 ...
Страница 202: ...Index AXP 1410 Installation and Use 6806800H70F 202 ...
Страница 203: ......