background image

 

 

Operating instruction 

M36 series 3-way solenoid valves 

 

 

 

Emerson Climate Technologies GmbH  

www.emersonclimate.eu

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 06.07.2016 

M36_OI_ML_R04_865127.docx 

G e n e r a l   i n f o r m a t i o n :  

The M36 series 3-way solenoid valve is designed to 
switch the flow of refrigerant. The typical application 
is to switch between an external condenser and an 
internal coil for heat recovery purposes. 

  S a f e t y   i n s t r u c t i o n s :  

 

Read operating instructions thoroughly. Failure 
to comply can result in device failure, system 
damage or personal injury. 

 

According to EN 13313 it is intended for use by 
persons having the appropriate knowledge and 
skill. 

 

Before opening any system make sure pressure 
in system is brought to and remains at 
atmospheric pressure. 

 

In a severely contaminated system, avoid 
breathing acid vapors and avoid contact with 
skin from contaminated refrigerant / lubricants. 
Failure to do so could result in injury. 

 

Do not release any refrigerant into the 
atmosphere! 

 

Do not exceed the specified maximum ratings for 
pressure, temperature, voltage and current. 

 

Ensure that the system piping is grounded. 

 

Before installation or service disconnect all 
voltages from system and device. 

 

Warning:  Do not use the valve as a safety shut-
off valve for service purposes. 

 

Do not operate system before all cable 
connections are completed. 

 

Do not use any other fluid media without prior 
approval of EMERSON. Use of fluids not listed 
could result in: Change of hazard category of 
product and consequently change of conformity 
assessment requirement for product in 
accordance with European pressure equipment 
directive 97/23/EC. 

 

Ensure that design, installation and operation 
are according to European and national 
standards/regulations. 

M o u n t i n g   l o c a t i o n :   ( F i g .   1 , 2 )  

 

A = Inlet connection; B = Outlet connection to 
condenser; C = Outlet connection to Heat Reclaim; 
D = Pilot connection to suction line 

 

Valves may be mounted in horizontal or vertical 
lines.  

 

Up-side down position is not allowed and can cause 
mal-function.  

 

The Pilot connection has to be connected to suction 
line  (Fig.2). In addition, the suction connection 
should be mounted in such a position to avoid any 
oil or contaminants being trapped inside the valve. 

 

Allow sufficient clearance above the valve for 
removal of Coil. 

I n s t a l l a t i o n :  

 

Do not remove seal caps until ready for installation 
in order to minimize entering of moisture and dirt. 
Avoid damaging the connections! 

 

Do not dent, bend, or use the enclosing tube as a 
lever. A damaged enclosing tube may result in coil 
burnout, inoperative valve or leakage.  

 

Direction of flow must match with the arrow on the 
valve body. 

 

Internal parts must be protected from foreign 
material and moisture. EMERSON filter-drier use in 
liquid line and EMERSON filter use in suction line 
is recommended. 

 

Tighten the nut of the pilot  connection to a max. 
torque of 8Nm. Always use a spanner on the body 
connection to prevent excessive torque. 

B r a z i n g :   ( F i g .   3 )  

 

Perform and consider the brazing joint as per 
EN 14324. 

 

Do not disassemble valve before brazing. 

 

Before and after brazing clean tubing and brazing 
joints. 

 

The use of appropriate brazing material is required 
(soft solder is not allowed). 

 

To avoid oxidization, it is advised to purge the 
system with an inert gas such as nitrogen while 
brazing. 

 

Never use oxygen or flammable gases. 

 

Do not exceed the max. body temperature of 
120°C!

 

I n s t a l l a t i o n   C o i l :  

 

For mounting of the ASC3 coil please refer to coil 
operating instruction. 

T e s t i n g :  

•  Before Testing let the parts cool down to a 

temperature < 40°C. 

•  Cycle valve several times. A distinct click should be 

heard each time the solenoid is energized. 

Note:

 EMERSON solenoid valves are equipped with a 

continuous-duty coil, which when energized for an 
extended period of time becomes hot. This is normal. 

P r e s s u r e   T e s t :  

After completion of installation, a pressure test must 
be carried out as follows: 
-

 

according to EN 378 for systems which must 
comply with European pressure equipment directive 
97/23/EC. 

-

 

to maximum working pressure of system for other 
applications. 

 

Warning

:  

 

Failure to do so could result in loss of refrigerant 
and personal injury. 

 

The pressure test must  be conducted by skilled 
persons with due respect regarding the danger 
related to pressure. 

L e a k a g e   T e s t :  

Conduct a  tightness test according to EN 378-2 with 
appropriate equipment and method to identify 
leakages of external joints. 

O p e r a t i o n :  

Application  note: The coil must be energized during 
pump-down or compressor shut-down. 

S e r v i c e   /   M a i n t e n a n c e :  

Fully depressurize Valve. After reducing pressure to 
atmospheric the valve may be opened and internal 
parts removed and replaced. Install parts in reverse 
sequence as removed.

  

T e c h n i c a l   D a t a :    

 

Maximum Operating Pressure Differential 
 

 

            MOPD: 28 bar (400 psi) 

 

Maximum working pressure PS:   34.5 bar (500 psi)  

 

Medium temperature:  

   -40…+120°C 

 

Refrigerants: R22, R404A, R507, R134a, R407C, 
R502, R12, R448A, R49A, R450A, R513A and 
R1234ze. Not suitable for R11 or Ammonia,  

 

Marking:   

  

 

The valves do not require CE marking 

 

 
 

Содержание Alco Controls M36 Series

Страница 1: ... Avoid damaging the connections Do not dent bend or use the enclosing tube as a lever A damaged enclosing tube may result in coil burnout inoperative valve or leakage Direction of flow must match with the arrow on the valve body Internal parts must be protected from foreign material and moisture EMERSON filter drier use in liquid line and EMERSON filter use in suction line is recommended Tighten t...

Страница 2: ...ge damit keine Feuchtigkeit und Verunreinigungen in den Filter Trockner eindringen können Anschlüsse nicht beschädigen Das Ankerrohr vor jeglichen Beschädigungen schützen Ein defektes Ankerrohr kann zu Fehlfunktion Undichtigkeit oder zum Durchbrennen der Magnetspule führen Die Flussrichtung muss mit dem Pfeil auf dem Ventilkörper übereinstimmen Zum Schutz des Ventils vor Verunreinigungen und evtl ...

Страница 3: ...mmager les connexions Ne pas écraser plier ou utiliser le tube magnétique comme un levier Celà peut entrainer un grillage de la bobine un non fonctionnement de la vanne ou des fuites Respecter le sens du fluide indiqué sur le corps de vanne par un flèche Le mécanisme interne doit être protégé de la pollution et de l humidité L utilisation d un filtre déshydrater EMERSONS sur la ligne liquide ou d ...

Страница 4: ...a Insta la ci ó n Extraíga los tapones de protección justo en el momento de la instalación para reducir la posible entrada de humedad y suciedad Evite dañar las conexiones No golpee doble ni utilice el vástago de la válvula solenoide como una palanca Un daño en dicho vástago puede provocar que la bobina se queme que la válvula deje de funcionar o se produzcan fugas La dirección de flujo debe coinc...

Страница 5: ... come leva il tubo di chiusura Un tubo di chiusura danneggiato può causare la bruciatura della bobina il malfunzionamento della valvola o perdite La direzione del flusso deve corrispondere alla freccia sul corpo valvola L interno della valvola deve essere protetto da sporcizia e umidità E raccomandato l uso di filtri essiccatori EMERSON sia sulla linea del liquido che in aspirazione Serrare il dad...

Страница 6: ...гайте повреждения соединений Не сминать не сгибать и не использовать трубку штока вентиля как рычаг Повреждение штока может привести к сгоранию катушки выходу из строя клапана или к утечке Направление потока должно соответствовать стрелке на корпусе клапана Внутренние части должны быть защищены от инородных частей и загрязнений Рекомендуется использовать фильтры осушители EMERSON на линиях всасыва...

Страница 7: ...M36 Emerson Climate Technologies GmbH www emersonclimate eu Am Borsigturm 31 I 13507 Berlin I Germany Date 06 07 2016 M36_OI_ML_R04_865127 docx Fig Рис 1 Fig Рис 2 Fig Рис 3 ...

Отзывы: