S4K2U-5C SEriES USEr mAnUAL |
43
Table 11: UPS Specifications
Parameters
Model
S4K2U1000-5C
S4K2U2000-5C
S4K2U3000-5C
Operating elevation
Up to 3,000 m [10,000 ft.]
Storage elevation
15,000 m [50,000 ft.] max.
Audible noise
<43 dBA max. @ 1 m [3 ft.] front
& sides; <46 dBA max. @ 1 m [3
ft.] rear
<48 dBA max. @ 1 m [3 ft.] front & sides;
<48 dBA max. @ 1 m [3 ft.] rear
AGENCy
Safety
EC/En/AS 62040-1-1:2008
model S4K2U3000-5C only: cULus Listed: UL 1778, CSA 22.2 no. 107.3 not for use in a computer room as
defined in AnSi/nFPA 75, the Standard for the Protection of Electronic Computer/Data Processing Equipment
RFI/EMI
iEC/En/AS 62040-2 2
nd
Ed. = CiSPr22 Class A
Surge immunity
iEC62040-2 2
nd
Ed.
Transportation
iSTA Procedure 1A
Table 12: Battery Cabinet Specifications
Parameters
Model Number
S4K2U48BATC
S4K2U96BATC
Used with UPS models
S4K2U1000-5C, S4K2U2000-5C
S4K2U3000-5C
DIMENSIONS, D x W x H
Unit
497 x 430 x 85 mm [19.6 x 16.9 x 3.3 in.]
602 x 430 x 85 mm [23.7 x 16.9 x 3.3 in.]
Shipping
717 x 570 x 262 mm [28.2 x 22.4 x 10.3 in.]
717 x 570 x 262 mm [28.2 x 22.4 x 10.3 in.]
WEIGHT
Unit
32.0 kg [70.5 lb.]
42.4 kg [93.5 lb.]
Shipping
35.0 kg [77.2 lb.]
46.0 kg [101.4 lb.]
BATTERy PARAMETERS
Type
Valve-regulated, non-spillable, lead acid
Qty x V x Rating
2 x 4 x 12 V x 9.0 Ah
2 x 6 x 12 V x 9.0 Ah
Battery mfr./Part number
CSB/UPS12460
Backup time
See Table 14
ENVIRONMENTAl REqUIREMENTS
Operating temperature
0°C to +40°C [+32°F to +104°F]; see Table 13 for operating temperature parameters
Storage temperatures
-15°C to +50°C [+19°F to +104°F]
Relative humidity
0% to 95%, non-condensing
Operating elevation
Up to 3,000 m [10,000 ft.]
Storage elevation
15,000 m [50,000 ft.] max.
AGENCy
Safety
CE: iEC/En 62040-1:2008; cULus Listed: UL 1778, CSA 22.2 no. 107.3
RFI/EMI
iEC/En/AS 62040-2 2
nd
Ed. = CiSPr22 Class A
Surge immunity
iEC62040-2 2
nd
Ed.
Transportation
iSTA Procedure 1A