42
| 9.0
Specifications
9.0 Specifications
Table 11: UPS Specifications
Parameters
Model
S4K2U1000-5C
S4K2U2000-5C
S4K2U3000-5C
DIMENSIONS, D x W x H
Unit
497 x 430 x 85 mm [19.6 x 16.9 x 3.3 in.]
602 x 430 x 85 mm [23.7 x 16.9 x 3.3 in.]
Shipping
717 x 570 x 262 mm [28.2 x 22.4 x 10.3 in.]
717 x 570 x 262 mm [28.2 x 22.4 x 10.3 in.]
WEIGHT
Unit
16.8 kg [37.0 lb.]
23.2 kg [51.1 lb.]
32.4 kg [71.4 lb.]
Shipping
20.0 kg [44.1 lb.]
26.0 kg [57.3 lb.]
36.0 kg [79.4 lb.]
INPUT AC PARAMETERS
Voltage range
230 VAC nominal; variable based on output load
90% to 100% Loading
177 VAC/280 VAC
196 VAC/280 VAC
70% to 90% Loading
168 VAC/280 VAC
184 VAC/280 VAC
30% to 70% Loading
150 VAC/280 VAC
161 VAC/280 VAC
0% to 30% Loading
115 VAC/280 VAC
115 VAC/280 VAC
Power factor
0.99
Frequency
40 Hz to 70 Hz; auto sensing
Input power receptacle
iEC 320 C14
iEC 320 C20
OUTPUT AC PARAMETERS
Output receptacles
iEC 320 C13 x 6
iEC 320 C13 x 6; iEC 320 C19 x 1
Voltage
200/208/220/230/240 VAC (user-configurable) ±3%
Frequency
50 Hz or 60 Hz
Waveform
Sine wave
Overload
200% for 2 seconds; 150%
for 1 minute with transfer to
bypass
200% for 2 seconds; 150% for
50 seconds with transfer to
bypass
200% for 2 seconds; 150% for 55 seconds
with transfer to bypass
Power factor
0.90
BATTERy
Type
Valve-regulated, non-spillable, lead acid
Qty x V x Rating
4 x 12 V x 5.0 Ah
4 x 12 V x 9.0 Ah
6 x 12 V x 9.0 Ah
Battery mfr./Part number
CSB/Hr1221W
CSB/UPS12460
Backup time
See Table 14
Recharge time
3 hours to 90% capacity after full discharge with 100% load until UPS auto shutdown (internal batteries only)
ENVIRONMENTAl REqUIREMENTS
Operating temperature
0°C to +40°C [+32°F to +104°F]; see Table 13 for operating temperature parameters
Storage temperatures
-15°C to +50°C [+5°F to +122°F]
Relative humidity
0% to 95%, non-condensing