The ON/OFF Function
Parameters • 9
DISPLAY
CF
Temperature measurement unit
°C =
Celsius
°F
= Fahrenheit
(
CAUTION!
When the measurement unit is changed, the setpoint and the values of the
parameters
Hy
,
LS
,
US
,
ot
,
ALU
and
ALL
have to be checked and modified if neces-
sary).
rES
Resolution (for °C)
(
in
= 1°C;
dE
= 0.1°C)
Allows decimal point display.
Lod
Device display
(
P1
;
P2
,
P3
,
P4
,
SEt
,
dtr
)
Selects which probe is displayed by the device:
P1
= Thermostat probe
P2
= Evaporator probe;
P3
= Third probe (only for models with this option enabled)
P4
= Fourth probe
SEt
= setpoint
dtr
= percentage of visualization
Red
X- REP display (optional)
(
P1
;
P2
,
P3
,
P4
,
SEt
,
dtr
)
Selects which probe is displayed by X- REP:
P1
= Thermostat probe
P2
= Evaporator probe
P3
= Third probe (only for model with this option enabled)
P4
= Fourth probe
SEt
= setpoint
dtr
= percentage of visualization
dLy
Display delay
(0 to 20.0 min; resul. 10 seconds)
When the temperature increases, the display is updated of 1°C/1°F after this time.
dtr
Percentage of the second and
first probe for visualization
when
Lod
=
dtr
(0 to 100; 100
=
P1
, 0 =
P2
)
If
Lod = dtr
,
it allows to set the visualization according to the percentage of the first and
second probe, as for the following formula (dtr(
P1
-
P2
)/100 +
P2
).
DEFROST
EdF
Defrost mode (only for control-
ler with RTC)
rtC
= Real Time Clock mode. Defrost time follows
Ld1
to
Ld6
parameters on work-
days and
Sd1
to
Sd6
on holidays.
in =
interval mode. The defrost starts when the time
Idf
is expired.
tdF
Defrost type
EL
= electrical heater
in
= hot gas
dFP
Probe selection for defrost ter-
mination
nP
= no probe
P1
= thermostat probe
P2 =
evaporator probe
P3
= configurable probe
P4
= probe on Hot Key plug
dtE
Defrost termination tempera-
ture
(-50 to 50°C/ -58 to 122°F) (Enabled only when
EdF
=
Pb
)
Sets the temperature measured by the evaporator probe, which causes the end of defrost.
IdF
Interval between defrost cycles
(0 to 120 hr)
Determines the time interval between the beginning of two defrost cycles.
MdF
(Maximum) length for defrost
(0 to 255 min)
When
P2P = n
, (not evaporator probe: timed defrost) it sets the defrost duration, when
P2P
=
y
(defrost end based on temperature) it sets the maximum length for defrost.
dSd
Start defrost delay
(0 to 99 min)
This is useful when different defrost start times are necessary to avoid overloading the
plant.
Code
Parameter
Function
Table 7-1
- List of Parameters