The ON/OFF Function
Parameters • 11
ArP
Probe selection for auxiliary
nP
= no probe, the auxiliary relay is switched only by the digital input
P1 =
Probe 1 (thermostat probe)
P2 =
Probe 2 (evaporator probe)
P3 =
Probe 3 (display probe)
P4 =
Probe 4
Sdd
Auxiliary relay OFF during de-
frost
n =
the auxiliary relay operates during defrost
y =
the auxiliary relay is switched OFF during defrost
ALARMS
ALP
Probe selection for alarm
nP
= no probe, the temperature alarms are disabled
P1 =
Probe 1 (thermostat probe)
P2 =
Probe 2 (evaporator probe)
P3 =
Probe 3 (display probe)
P4 =
Fourth probe
ALC
Temperature alarms configura-
tion
(
Ab
;
rE
)
Ab
= absolute temperature: alarm temperature is given by the
ALL
or
ALU
values.
rE
= temperature alarms are referred to the setpoint. Temperature alarm is enabled when
the temperature exceeds the
SEt
+
ALU
or
SEt
-
ALL
values.
ALU
Maximum temperature alarm
(
SEt
to 150°C;
SEt
to 302°F)
When this temperature is reached, the alarm is enabled, after the
ALd
delay time.
ALL
Minimum temperature alarm
(-100 to
SEt
; -148°C to 230°F)
When this temperature is reached, the alarm is enabled, after the
ALd
delay time.
AFH
Differential for temperature
alarm recovery
(0.1 to 25.5°C; 1 to 45°F)
Intervention differential for recovery of temperature alarm. It is also used for the restart
of the fan when the
FSt
temperature is reached.
ALd
Temperature alarm delay
(0 to 255 min)
Time interval between the detection of an alarm condition and alarm signaling.
dAo
Exclusion of temperature alarm
at start-up
(from 0.0 min to 23.5 hr)
Time interval between the detection of the temperature alarm condition after device
power ON and alarm signaling.
CONDENSER TEMPERATURE ALARM
AP2
Probe selection for temperature
alarm of condenser
nP
= no probe
P1
= thermostat probe
P2 =
evaporator probe
P3
= configurable probe
P4
= probe on Hot Key plug
AL2
Low temperature alarm of con-
denser
(-100 to 150°C)
When this temperature is reached, the
LA2
alarm is signaled, possibly after the
Ad2
de-
lay.
AU2
High temperature alarm of con-
denser
(-100 to 150°C)
When this temperature is reached, the
HA2
alarm is signaled, possibly after the
Ad2
de-
lay.
AH2
Differential for temperature
condenser alarm recovery
(0.1 to 25.5°C; 1 to 45°F)
Ad2
Condenser temperature alarm
delay
(0 to 255 min)
Time interval between the detection of the condenser alarm condition and alarm signal-
ing.
dA2
Condenser temperature alarm
exclusion at start up
(from 0.0 min to 23.5 hr, res. 10 min)
bLL
Compressor OFF with low tem-
perature alarm of condenser
n = no
:
compressor keeps on working
Y = yes
,
compressor is switched OFF until the alarm is present, in any case regulation
restarts after
Ac
time at minimum.
Code
Parameter
Function
Table 7-1
- List of Parameters