28 • XR75CX I&O Manual
Fnc
Fan operating mode
C-n
,
O-n
,
C-y
,
O-y
O-n
Pr1
Fnd
Fan delay after defrost
0 to 255 min
10
Pr1
FCt
Differential of temperature for forced
activation of fans
0 to 50°C
10
Pr2
FSt
Fan stop temperature
-50 to 50°C/-58 to 122°F
2
Pr1
Fon
Fan ON time with compressor OFF
0 to 15 (min)
0
Pr2
FoF
Fan OFF time with compressor OFF
0 to 15 (min)
0
Pr2
FAP
Probe selection for fan management
nP
;
P1
;
P2
;
P3
;
P4
P2
Pr2
ACH
Kind of action for auxiliary relay
CL
;
Ht
CL
Pr2
SAA
Setpoint for auxiliary relay
-100 to 110°C / -58 to 230°F
0.0
Pr2
SHy
Differential for auxiliary relay
0.1 to 25.5°C / 1 to 255°F
2.0
Pr2
ArP
Probe selection for auxiliary relay
nP
/
P1
/
P2
/
P3
/
P4
nP
Pr2
Sdd
Auxiliary relay operating during defrost
n
to
y
n
Pr2
ALP
Alarm probe selection
nP
;
P1
;
P2
;
P3
;
P4
P1
Pr2
ALC
Temperature alarms configuration
rE
= related to set;
Ab
= absolute
Ab
Pr2
ALU
Maximum temperature alarm
SEt
to 110.0°C;
SEt
to 230°F
110.0
Pr1
ALL
Minimum temperature alarm
-100°C to
SEt
/ -58°F to
SEt
-50.0
Pr1
AFH
Differential for temperature alarm recovery
(0.1°C to 25.5°C) (1°F to 45°F)
2.0
Pr2
ALd
Temperature alarm delay
0 to 255 min
15
Pr2
dAo
Delay of temperature alarm at start up
0 to 23 hr and 50’
1.3
Pr2
AP2
Probe for temperature alarm of condenser
nP
;
P1
;
P2
;
P3
;
P4
P4
Pr2
AL2
Condenser for low temperature alarm
(-100 to 150°C) (-67 to 302°F)
-40
Pr2
AU2
Condenser for high temperature alarm
(-100 to 150°C) (-67 to 302°F)
110
Pr2
AH2
Differ. for condenser temp. alarm recovery
(0.1°C to 25.5°C) (1°F to 45°F)
5
Pr2
Ad2
Condenser temperature alarm delay
0 to 254 min, 255 =
not used
15
Pr2
dA2
Delay of cond. temperature alarm at start up
0.0 to 23 hr 50’
1.3
Pr2
bLL
Compressor OFF for condenser low tempera-
ture alarm
n
(0) -
Y
(1)
n
Pr2
AC2
Compressor OFF for condenser high tempera-
ture alarm
n
(0) -
Y
(1)
n
Pr2
tbA
Alarm relay disabling
n
= no;
y
= yes
y
Pr2
oA3
Fourth relay configuration
ALr
= alarm;
dEF
= do not select
it;
Lig
= Light;
AUS
=AUX;
onF
= always ON;
Fan
= do not select
it;
db
= neutral zone;
cP2
= second
compressor;
dF2
= do not select it;
HES
= night blind
Lig
Pr2
AOP
Alarm relay polarity (
oA3
=
ALr
)
oP
;
CL
CL
Pr2
i1P
Digital input polarity (18-20)
oP
= opening;
CL
= closing
CL
Pr1
i1F
Digital input 1 configuration (18-20)
dor
;
dEF
dor
Pr1
i2P
Digital input polarity (18-19)
oP
= opening;
CL
= closing
CL
Pr2
i2F
Digital input configuration (18-19)
EAL
-
bAL
-
PAL
-
dor
-
dEF
-
ES
-
AUS
-
Htr
-
FAn
-
HdF
-
onF
EAL
Pr2
did
Digital input alarm delay (18-20)
0 to 255 min
15
Pr1
Label
Name
Range
Value
Level
Table 19-1
- Default Setting Values (
*
Only for models with real time clock (RTC),
2
Only for XR75CX with X-REP output)