Ensure that there is no obstruction of airflow into or out of the unit. Remove obstacles, which block air
intake or discharge
!
The location must be well ventilated, so that the unit can draw in and distribute plenty of air thus lowering
the condensing temperature.
!
A place capable of bearing the weight of the outdoor unit and isolating noise and vibration
!
A place protected from direct sunlight. Otherwise use and awning
for protection, if necessary.
!
The location must not be susceptible to dust or oil mist.
INSTALLATION CLEARANCE
!
Outdoor unit must be installed such that there is no shot circuit of
the hot discharge air or obstruction to smooth airflow. Select
The coolest possible places where intake air should not be hotter than the outside temperature.
ALL MODELS
A
B
C
D
Minimum Distance
300 mm
1000 mm
300 mm
500 mm
CAUTION
If the condensing unit is operated in an atmosphere containing oils (including machine oils), salt (coastal area), sulphur
gas (near hot spring, oil refinery plant), such substances may lead to failure of the unit.