5.6) Normally, the R407C cylinder or can is being equipped with, a dip-pipe for liquid withdrawal. However, if
the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the bottom.
5.7) When servicing leak, the top up method, commonly practice for R22 system, is not recommended for
R407C system, Unlike R22 where the refrigerant is of a single component, the composition of R407C, Which made-
up of three different component, may have changed during the leak. Consequently, a top-up may not ensure that the
R407C in the system is of original composition. This composition shift may adversely affect the system performance.
It is recommended that the system should be evacuated thoroughly before recharging with R407C.