M -Bus Split t er

 

Share up to 4 M-Bus slaves 

Int roduct ion 

The M-Bus Splitter allows two parties to have access to the sam e 
main m eter. Two M-Bus m asters can be connected to the meter 
and register readings individually. 
This m anual provides the information needed to get started with 
the M-Bus Splitter.  

For a com plete description of the product, download the manual 
from Elvaco AB w eb site, w w w.elvaco.com. 

Overview  

4

3

2

1

5

6

7

8

 

 

 

 

 
M -Bus 2-w ire syst em  

M-Bus is a multi-drop 2-w ire bus with no polarity. Use a cable of 
area 0.25-1.5 mm

2

, e.g. a standard telephone cable (EKKX 

2x2x0.5). 

M ount ing 

M-Bus Splitter can be mounted on a DIN-rail or directly on the 
wall. For w all mounting, the black m ounting bracket on the back 

of the M -Bus Splitter has to be dem ounted from  the unit and 
mounted on the wall. The M-Bus Splitter will then be snapped on 
to the black m ounting bracket. 

1.

 

24 V pow er supply should be connected when more than 
one m eter is connected or if the Splitter does not 
manage to operate the connected m eter.  

2.

 

Connect m eter on the terminal m arked w ith M-Bus IN
The m eters m ust have unique primary addresses 
between 1 and 250. 

3.

 

Connect M-Bus m aster on the terminals marked with M-

Bus OUT2 and OUT1. M-Bus OUT2 must be connected 
as it provides power to the Splitter. 
 

M-Bus Splitter

M-Bus 2-wire

to M-Bus master 1

M-Bus 2-wire

to M-Bus master 2

24-35 VAC
30-40 VDC

Max. 4 M-Bus meters

 

Operat ion 

When the Splitter is powered up it takes up to 5 minutes before it 
is ready to use since it needs charging. During charging, all LEDs 
will flash four short flashes in order every three seconds. 

1.

 

There are four settings to be done to adapt the Splitter to 
the installation. This is done by setting the jumpers in on 
or off mode. See Settings for m ore information. 

2.

 

Start the meter installation by changing the position of 
any jumper (off to on/on to off). Put the jumper back to 
its original position. See settings. 

3.

 

During scanning, the LED for M-Bus IN flashes with a 
short flash every second. Depending on the scanning 
speed the scanning time varies from 1 to 8 minutes.  

4.

 

When the scanning is completed, the M-Bus Splitter is in 
norm al operation. See LED indications. 

Troubleshoot ing 

Make sure that: 

1.

 

All cables are connected properly, both on the M-Bus 
Splitter and on the M-Bus m aster. 

2.

 

The voltage on M-Bus IN is greater than 23 VDC. If the 
voltage is lower, disconnect one m eter at a tim e to find 

the failing m eter. 

3.

 

The voltage on M-Bus OUT2 is greater than 26 VDC. If 
the voltage is not w ithin this range, check the function of 
the M-Bus master. Connect external 24 VAC power 
supply when connecting more than one meter. When 
low  voltage is detected on M-Bus IN, all LEDs flashes 
four times. 

4.

 

The connected M-Bus m eters all have unique prim ary 
addresses. 

5.

 

Contact the supplier if the error remains.

1. Screw term inal M-Bus OUT1 - Isolated 
2. LED M-Bus OUT1 - Isolated 
3. LED M-Bus IN 
4. Screw term inal M-Bus IN 
5. Configuration jumpers 
6. Screw term inal external power 
7. LED M-Bus OUT2 - Pow er 
8. Screw term inal M-Bus OUT2 - Pow er 