CMi6110
User’s Manual English
CMi6110 User’s Manual English
page | 20 (42)
[2022-10]
v1.3
Op.
LwM2M object
LwM2M resource
ID
Type
Range or
Enumeration
Comment
R
Elvaco
Transaction
statistics
Average response
time
33910/./4
Integer
R
Elvaco
Transaction
statistics
Minimum
response time
33910/./5
Integer
R
Elvaco
Transaction
statistics
Maximum
response time
33910/./6
Integer
Table 2: Elvaco and product specific LwM2M objects
6.3.1 L+G UH50 error codes
L+G UH50 meter specific error codes are listed in Table 3. Make sure to double check error codes
identifier and explanation with latest meter specification.
Bit-No
Identifier
Explanation
0
F0
Error during flow metering (e.g. Air in measuring pipe)
1
F1
Interruption of flow temperature sensor
2
F2
Interruption of return temperature sensor
3
F3
Electronic for temperature evaluation defective
4
F4
1
Meter battery empty
5
F5
Short-circuit flow temperature sensor
6
F6
Short-circuit return temperature sensor
7
F7
Fault in the internal memory (CRC)
8
F8
Error F1, F2, F5 or F6 pending for longer than 8h.
9
F9
Error in the electronics
10
F0V
Prewarning for soiling of the measurement tube
11
F7V
2
Correctable error in the internal memory EEPROM 2
Table 3: UH50 error codes (TKB3448 V1.1 2008-10-06)
6.4 Changing APN via the DM system
Since changing APN is a potentially hazardous operation that may render the device disconnected from
the mobile network, there is a rollback functionality in place when changing the APN.
To change APN, write the APN to the resource /10/1/1 and set APN mode to manual in /10/1/2. Once
done, stage the changes by executing /33906/0/15. When executed, the device will reset and try to use
the new APN. If the device manages a successful bootstrapping, the new APN will be saved as the
default. If a successful bootstrapping has not happened for some time, the device will roll back to the old
APN and reset again.