CMi6110
User’s Manual English
CMi6110 User’s Manual English
page | 26 (42)
[2022-10]
v1.3
DIB
Field
Size
Data type
Description
5
Power
4 bytes
INT16
Power (W)
022Bxxxxxx = xxxxxx * 0.001 kW (W)
022Cxxxxxx = xxxxxx * 0.01 kW
022Dxxxxxx = xxxxxx * 0.1 kW
022Exxxxxx = xxxxxx kW
6
Flow
4 bytes
INT16
Flow (m
3
/h)
023Bxxxxxx = xxxxxx * 0.001 m
3
/h
023Cxxxxxx = xxxxxx * 0.01 m
3
/h
023Dxxxxxx = xxxxxx * 0.1 m
3
/h
023Exxxxxx = xxxxxx m
3
/h
7
Fw temp
4 bytes
INT16
Forward temperature (°C)
025Axxxx = xxxx * 0.1 °C
025Bxxxx = xxxx * °C
8
Rt temp
4 bytes
INT16
Return temperature (°C)
025Exxxx = xxxx * 0.1 °C
025Fxxxx = xxxx °C
9
Error flags
5 bytes
INT16
Error and warning flags
02FD17xxxx
For further information about Error flags please
refer to table 2 or the latest meter’s manual
10* Tariff 1
Energy
7 bytes
INT32
Tariff 1 Energy consumption (Wh, J)
841003xxxxxxxx = xxxxxxxx Wh
841003xxxxxxxx = xxxxxxxx * 10 Wh
841003xxxxxxxx = xxxxxxxx * 100 Wh
841003xxxxxxxx = xxxxxxxx kWh
841003xxxxxxxx = xxxxxxxx *10 kWh
841003xxxxxxxx = xxxxxxxx MJ
841003xxxxxxxx = xxxxxxxx * 10 MJ
11* Tariff 2
Energy
7 bytes
INT32
Tariff 2 Energy consumption (Wh, J)
842003xxxxxxxx = xxxxxxxx Wh
842003xxxxxxxx = xxxxxxxx * 10 Wh
842003xxxxxxxx = xxxxxxxx * 100 Wh
842003xxxxxxxx = xxxxxxxx kWh
842003xxxxxxxx = xxxxxxxx *10 kWh
842003xxxxxxxx = xxxxxxxx MJ
842003xxxxxxxx = xxxxxxxx * 10 MJ