CMi413
0 User’s Manual English
CMi413
0 User’s Manual English
page | 18 (25)
[2020-06]
V1.1
As for all
Scheduled
message formats, the transmit interval can only be set to the values included in
Table 10.
A detailed description of the payload in the message format is presented in Table 12.
DIB
Field
Size
Data type
Description
0
Message
format
1 byte
-
0x13 (Scheduled
– Extended)
1
Energy
6 bytes
INT32
Energy consumption (Wh, J)
0403xxxxxxxx = xxxxxxxx Wh
0404xxxxxxxx = xxxxxxxx * 10 Wh
0405xxxxxxxx = xxxxxxxx * 100 Wh
0406xxxxxxxx = xxxxxxxx kWh
0407xxxxxxxx = xxxxxxxx * 10 kWh
040Exxxxxxxx = xxxxxxxx MJ
040Fxxxxxxxx = xxxxxxxx * 10 MJ
2
Volume
6 bytes
INT32
Volume (m
3
)
0413xxxxxxxx = xxxxxxxx * 0.001 m
3
0414xxxxxxxx = xxxxxxxx * 0.01 m
3
0415xxxxxxxx = xxxxxxxx * 0.1 m
3
0416xxxxxxxx = xxxxxxxx m
3
0417xxxxxxxx = xxxxxxxx * 10 m
3
3
Power / Flow
/ Fw temp /
Rt temp
12 bytes
INT64
Byte 0-2 = DIF/VIF codes, 0x07FFA0
Byte 3 = Scaling of Power/Flow
- Bit 6..4 (n), 10
n-3
W, n = 0..7
- Bit 2..0 (m), 10
m-6
litres/h, m = 0..7
Byte 4-5 = Fw temp (lsByte -> msByte), °C, 2
decimals
Byte 6-7 = Rt temp (lsByte -> msByte), °C, 2
decimals
Byte 8-9 = Flow (lsByte -> msByte), 10
m-3
m
3
/h
Byte 10-11 = Power (lsByte -> msByte), 10
n-3
W
4
Meter ID/
Alarm codes
9 bytes
INT48
Byte 0-2 = DIF/VIF codes, 0x06FF21
Byte 3-4 = Alarm codes (lsByte -> msByte)
Byte 5-8 = Meter ID (lsByte -> msByte)