CMi413
0 User’s Manual English
CMi413
0 User’s Manual English
page | 11 (25)
[2020-06]
V1.1
Set absolute
time
Sets the time of the meter.
N/A
Writeable
N/A
N/A
Set Time
Relative
Adjusts the time of the meter
relative to the current time.
N/A
N/A
N/A
Writeable
Set UTC
offset
Sets the UTC offset of the
meter.
N/A
Readable /
Writeable
Readable
Writeable
Configuration
Lock
Locks the module to prevent
unauthorized access.
Open
Readable /
Writeable
Readable
Writeable
LoRaWAN settings
Device EUI
Unique module identification
number. Not configurable.
Device-unique
64-bit number
Readable
Readable
N/A
Activation
type
Sets the way the device joins
the LoRaWAN network.
OTAA
Readable /
Writeable
Readable
N/A
Network join
Displays whether the module
has joined the LoRaWAN
network or not.
N/A
Readable
Readable
N/A
Join EUI
Application ID that determines
where data ends up.
0x 94 19 3A 03 09
00 00 01 (internal
antenna version)
0x 94 19 3A 03 0A
00 00 01 (external
antenna version)
Readable /
Writeable
Readable
N/A
Device
address
32-bit address used by the
module to identify itself on the
LoRaWAN network.
0x 00 00 00 00
Readable /
Writeable
N/A
N/A
Current data
rate
The current data rate used for
the module.
N/A
Readable
Readable
N/A
Table 2: Configuration options
6.4 Time handling
The module relies on the meter’s clock for keeping time. Time in the meter is assumed to be in standard
local time (no DST). When synchronizing time in the meter using the OTC App, local standard time is
always used, even if DST is in effect. The timestamped meter data sent from the module can be adjusted
to be sent in UTC by specifying the “UTC offset” configuration parameter. The UTC offset will be
subtracted from the timestamp prior to transmission. If the meter is in Sweden, which uses CET (Central
European Time), it should have UTC offset set to +60 (+1h). In this case at time 12.00 a telegram is sent
with timestamp 11.00 as this is the corresponding UTC time. A meter in New York (USA) should have a
UTC offset of -300 (-5h) etc. A UTC offset of 0 means the meter time is used as-is.
6.5 Adaptive data rate (ADR)
CMi4140 uses Adaptive Data Rate (ADR), part of the LoRaWAN standard, where the network server
determines the optimal rate of communication for the module based on current signal conditions. In best
case, the module will use its highest data rate (DR5) in order to be as energy efficient as possible. When