CMi413
0 User’s Manual English
CMi413
0 User’s Manual English
page | 21 (25)
[2020-06]
V1.1
Configuration
lock
0x05
0x01
0x00 = Locked
0x01 = Open
0x00050101
(Enables configuration
lock)
Transmit interval 0x06
0x02
0xNumber of minutes between
transmission
(lsByte -> msByte)
0x0006021E00
(Sets the Tx interval to
30 minutes)
Message format
0x07
0x01
0x0F = Message format
Standard
0x10 = Message format
Compact
0x11 = Message format
JSON
0x12 = Message format
Scheduled-daily redundant
0x13 = Message format
Scheduled - Extended
0x14 = Message format
Combined heat/cooling
0x00070110
(Sets the message
format to compact)
EcoMode
0x0F
0x01
0x00 = Disable EcoMode
0x01 = Enable EcoMode
0x000F0100
(Disables EcoMode)
Set Time
Relative
0x13
0x04
0xNumber of seconds*
(lsByte -> msByte)
*Negative numbers supported.
0x0013043C000000
(Adds 60 seconds to
the current time)
0x0013043C000080
(Subtracts 60 seconds
from the current time)
UTC offset
0x17
0x02
0xNumber of minutes* (lsByte
-> msByte)
*Negative numbers supported.
0x17023C00 (Sets the
UTC offset to +60
minutes)
0x17023C80 (Sets the
UTC offset to -60
minutes)
Reboot
0x22
0x02
0x759E is used to reboot
device (note endianness, LSB
first).
0x0022029E75
(Reboots the device)
Table 14: Downlink commands