![Eltek Smartpack2 Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/eltek/smartpack2/smartpack2_user-manual_2397251020.webp)
3 About Power System Configuration
20
User's Guide
Smartpack2 Master Controller
350020.013, Issue 2.0, 2014 Jan
7 - Commissioning options
This logical group presents a generic description of the steps required to carry out
commissioning tasks of the power system.
Refer also to the system’s user documentation, and to the Commissioning Procedure pull-
out list in the system’s quick start guide.
8 - Up/Download options (Data Storage Device)
The options in this logical group let you upload firmware from the controller’s data storage
device to connected controllers and control units, as well as download or save system
related logs, etc. to the data storage device.
NOTICE:
The
Smartpack2 Master
controller uses an external SD card as data storage device, and the
Smartpack S
controller uses
embedded Flash Memory.
In addition to firmware, this group’s options offer you the possibility of uploading and
saving system configuration files to the controller’s data storage device.
Uploading and downloading
is allowed
at this level, using the Pin-Code for the
Service
Access Level
.
NOTICE:
Using the
CWUI
(Controller Web-based User Interface) or
PowerSuite
you can also up/download to other storage media
(e.g. computer hard discs)
The Up- and Download options are organized in following groups:
Save Event Log
(system related log)
A command that saves to the controller’s data storage device a log of power
system events automatically registered by the system controller.
Read about “
Logs and Reports options
” on page 18
Save Data Log
(control unit related log)
A command that saves to the controller’s data storage device a log of key
system data (voltages, current and temperature values) registered by the
system controllers, or by other connected control units (e.g. I/O Monitor,
Mains Monitor)
Save Energy Log
(system related log)
A command that saves to the controller’s data storage device a log of the
power system’s energy usage, (Wh).
Save /Load Config
A command that saves to the controller’s data storage device a binary
formatted file <UNIT_nn.HEX> which contains the controller’s or any
connected CAN unit’s System Configuration, with all the specific parameters
and settings.
Also, you can upload a similar, specific System Configuration file
<UNIT_nn.HEX> to the controller or to any connected CAN unit, e.g. for
Содержание Smartpack2