UFM Series 6
Safety Instructions
Page 17 of 38
National and local regulations;
the SPU documentation (this manual, order specification stating the
type of entry holes) and on the SPU label;
the certificate and manual of the glands;
Specifications of the user wiring.
It is recommended to use suitable armoured shielded cable to provide
protection against mechanical damage and electrical interference.
Important!
Use a cable with suitable resistance, diameter, cores and length.
If your ultrasonic flow meter is FM approved (see the SPU label), these
special remarks are also applicable:
Installations shall comply with the relevant requirements of the
latest edition of the National Electrical Code (ANSI/NFPA 70).
Installations shall comply with the latest edition of the
manufacturer’s instruction manual.
For intrinsically safe installation in the United States of America,
electrical equipment connected to the Associated Apparatus shall
not use or generate more than 250 volts rms.
For guidance on installations in the United States of America, see
ANSI/ISA-RP12.06.01, Installation of Intrinsically Safe Systems for
Hazardous (Classified) Locations.
Tampering and replacement with non-factory components may
adversely affect the safe use of the system.
Seal fitting is required within 1.5 inches of enclosure.
Warning: See control drawing: 03.304.001.003.05/2 before
operating device. A copy of the control drawing is available in
Annex A – Control Drawing (FM)
(p.29).