EMS75VR-ROYAL-VENDING-INSTALLATION AND USER GUIDE-ISS3
Name
Description
Range
Default
11
Saving mode set point sets the lower
saving mode temperature (cut out
temperature).
0.0 to 9.9°C
(32 to 50°F)
7.0°C
(45°F)
12
Uninterrupted pull down the compressor
runs continually until the set point is
reached
0.0 to 30ºC
(32 to 86ºF)
20ºC
(68ºF)
13
Freeze-up protection is the temperature
to disable the compressor and enable
the evaporator fan to prevent freeze up
due to low temperature.
-15 to 10ºC
(5 to 50ºF)
0.0ºC
(32ºF)
14
Defrost interval is the period between
the end of a defrost cycle and beginning
of the next defrost cycle.
0 to 199 hours
06 hours
15
Defrost duration is the maximum time of
a defrost cycle.
1 to 199 minutes
15 minutes
16
Fan cycle on is the active period of the
evaporator fan while the compressor is
off.
1 to 30 minutes
30 minutes
17
Fan cycle off is the inactive period of the
evaporator fan while the compressor is
off.
1 to 30 minutes
1 minute
18
Alarm delay is the maximum time a door
can be open before sounding the alarm
buzzer.
00 to 30 minutes
00 (disabled)
19
Buzzer duration for open door alarm
conditions. After the buzzer duration, the
controller switches off the compressor.
1 to 254 seconds
60 seconds
20
Sensor enable enables the motion
sensor input.
00 (disabled) or 01 (enabled) 01 (enabled)
21
Display stability sets the rate of change
of the displayed temperature.
1 to 254
2
22
Defrost termination temperature defines
the temperature to end a defrost cycle.
1 to 30ºC
(33 to 86ºF)
9.0ºC
(48ºF)
23
Condenser high temperature is the
maximum permitted temperature
measured in the refrigeration system. On
reaching Ht, the controller disables the
compressor and activates an alarm
0.0 to 125ºC
(32 to 257ºF)
0.0 to 125ºC
(32 to 257ºF)