To  be  able  to  access  KNX,  the  KNX  PS640-IP  requires  an  additional  physical  address. 
This second physical address is only used for bus access and must be set up separately: 
Select  the  “Communication”  tab  under  Extras  ->  Options  in  the  ETS.  The 
communications  interface  is  the  connection  that  is  currently  configured.  Click  on 

Settings…

 to open the following window: 

 

 

 
Enter a physical address of your choice. This address should lie in the same topological 
line but should not be in use by another device. 
A dummy device may have to be added to the ETS project to reserve this address. 
 
 
 
 

Содержание KNX PS640-IP

Страница 1: ...ernet Interface Installation and Adjustment Elsner Elektronik GmbH Steuerungs und Automatisierungstechnik Herdweg 7 D 75391 Gechingen Germany Phone 49 0 70 56 93 97 0 Fax 49 0 70 56 93 97 20 info elsn...

Страница 2: ...ing position 9 Line reset 9 Data memory 10 Operating data 11 Language 11 Setting of parameters Software ETS 13 General 13 IP configuration 14 Routing KNX IP 16 Routing IP KNX 17 ETS Connection Manager...

Страница 3: ...X PS640 IP can be used as interface for accessing the bus via IP Like this the KNX system can be configuered and supervised from any PC in the LAN Tunnelling This device works according to the KNXnet...

Страница 4: ...function KNXnet IP Routing The Power Supply System KNX PS640 IP can operate as a line and or backbone coupler In both cases the LAN IP acts as a backbone KNX PS640 IP as a line coupler KNX PS640 IP a...

Страница 5: ...ology above it For example if a KNX PS640 IP has the physical address of 1 1 0 there must be no KNX IP Router with the address 1 0 0 The KNX PS640 IP has a filter table and thus contributes to reducin...

Страница 6: ...t circuit proof 24 V DC not reduced Output current max 150 mA LAN connector RJ45 10BaseT 10Mbit s Supported internet protocols ARP ICMP IGMP UDP IP and DHCP The following standards have been considere...

Страница 7: ...any mechanical damages In case of transport damage this must immediately notified to the supplier If damaged the power supply system must not be put into operation If an operation without risk may su...

Страница 8: ...and programming button 3 Bus connection KNX terminal 4 Input operating voltage 230 V AC L N PE 5 Output direct current voltage 24 V DC Connections 4 and 5 are suitable for solid conductors up to 1 5 m...

Страница 9: ...y once more in order to get into the sector Line reset Move the cursor flashing rectangle at right edge to the desired setting with the keys or and confirm with key Yes Reset is activated The line is...

Страница 10: ...yed With key you return to the previous menu level External overvoltage The number of external overvoltage incidents is displayed With key you return to the previous menu level Internal overvoltage Th...

Страница 11: ...the Operating Data menu with the keys and and confirm with key The current values of Bus voltage Bus current Temperature on the circuit board of the device are displayed With key you return to the pr...

Страница 12: ...e cursor to the desired language with the up and down keys and press the key The display automatically jumps to the previous menu in the desired language With key you get back by one menu level to the...

Страница 13: ...If a KNX failure is detected it is reported on the IP Return of the bus voltage is also reported IP address assignment automatic DHCP manual Automatic DHCP The IP address is automatically assigned on...

Страница 14: ...n IP The multicast IP address 224 0 23 12 was reserved KNXnet IP at the IANA Internet Assigned Numbers Authority for this purpose If a different multicast IP address is required it must lie within the...

Страница 15: ...be used in the local LAN the entry of 0 0 0 0 can remain unchanged Example of assigning IP addresses A PC is to be used to access the KNX PS640 IP IP address of the PC 192 168 1 30 Subnet of the PC 25...

Страница 16: ...block route Block No group telegrams of these main groups are routed to IP Route An additional page appears on which the routing of main groups 16 to 31 can be disabled or enabled in pairs Note The gr...

Страница 17: ...if they are routed to IP Answer with NACK Every received physically addressed telegram from KNX is responded to with NACK not acknowledge This means that communication with physically addressed telegr...

Страница 18: ...physically addressed telegram should be routed to KNX Broadcast telegrams block route Block No received broadcast telegrams are routed to KNX Route All received broadcast telegrams are routed to KNX...

Страница 19: ...as direct access to the particular line with this protocol Communication via IP takes place with a defined device here The ETS automatically searches for all KNXnet IP devices and displays them Select...

Страница 20: ...mmunication tab under Extras Options in the ETS The communications interface is the connection that is currently configured Click on Settings to open the following window Enter a physical address of y...

Отзывы: