Weather Station Suntracer KNX sl basic

 • Status: 26.08.2021 • Errors excepted. Subject to technical changes.

Wind sensor monitoring

: If the wind measurement value changes by less 

than ± 0.5 m/s within 48 hours, the maximum measurement value of 35 m/s is 
output as a fault message. All wind alarms with a limit value below 35 m/s 
become active as a result

Precipitation detection

: The sensor surface is heated, so that only drops and 

flakes are recognised as precipitation, but not mist or dew. When the rain or 
snow stops, the sensor is soon dry again and the precipitation warning ends

Temperature measurement

Frost protection for shading systems

Switching outputs

 for all measured and computed values. Threshold values 

can be adjusted per parameter or via communication objects

8 AND and 8 OR logic gates

, each with 4 inputs. All switching events as well 

as 16 logic inputs (in the form of communications objects) can be used as 
inputs for the logic gates. The output of each gate can be configured optionally 
as 1-bit or 2 x 8-bit

8 multi-function modules

 (computers) for changing the input data by 

calculations, by querying a condition or by converting the data point type

3.

Installation and start-up

3.1. Installation location

Select an installation position on the building where the sensors can measure wind,
rain and sunshine without hindrance. No structural elements should be mounted
above the weather station, from which water could continue to drop on the precipita-
tion sensor even after it has stopped raining or snowing. The weather station should
not be shaded by structures or, for example, trees. 

At least 60 cm of clearance must be left around the device. This facilitates correct wind
speed measurement without eddies. At the same time, this prevents spray (raindrops
hitting the device) or snow (snow penetration) from impairing the measurement. The
wind sensor must not come into contact with water. The distance also prevents birds
from biting the sensor.

The mounting position must be selected so that the sensors for rain and wind cannot
be touched by persons.

Please ensure that the extended awning does not cast shade on the unit, and that it is
protected from the wind.

Temperature measurements can also be distorted by external influences such as
warming or cooling of the building structure on which the sensor is mounted (sunlight,
heating or cold water pipes). Temperature variations from such sources of interference
must be corrected in the ETS in order to ensure the specified accuracy of the sensor
(temperature offset).

Содержание 70156

Страница 1: ...Suntracer KNX sl basic Weather Station Item number 70156 Installation and Adjustment EN...

Страница 2: ......

Страница 3: ...5 1 List of all communications objects 14 6 Parameter setting 25 6 0 1 Behaviour on power failure power restoration 25 6 0 2 Storage of threshold values 26 6 0 3 Malfunction objects 26 6 1 General se...

Страница 4: ...n this manual Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous situation which will lead to death or severe injuries if it is...

Страница 5: ...d operational start up tasks and only in the sur roundings designated for it Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating...

Страница 6: ...3 Installation and start up 3 1 Installation location Select an installation position on the building where the sensors can measure wind rain and sunshine without hindrance No structural elements sho...

Страница 7: ...ont of the de vice 60 cm Fig 2 The device must be attached to a vertical wall or a pole Place the supply line in a loop before leading it into the wall or junction box This will allow rain to drip off...

Страница 8: ...e transport sticker after installation Do not touch the sensor on the wind measuring element on bottom recessed 1 Brightness sensors 1 3 With alignment of the device to the south Sensor 1 East Sensor...

Страница 9: ...elease the screw joint of the mount with a cross headed screwdriver Wall installation 2 1 3 Fig 6 2 Sensor 1 East measurement directed outwards Sensor 2 South measurement directed vertically to the de...

Страница 10: ...ther station can be flexibly mounted on the wall Only use suitable fixing material screws dowels to fix the wall installation plate and make sure that the subsurface is stable Dimensions Fix Wall moun...

Страница 11: ...rew fastening Screw the sensor mounting plate onto the boom with the countersunk screw DIN 7991 M8x10 Place the Schnorr tooth lock washers between the mounting plate and the boom Fig 12 For mounting u...

Страница 12: ...on Suntracer KNX sl basic Status 26 08 2021 Errors excepted Subject to technical changes Installation examples Fig 14 Sensor offset upwards Fig 15 Sensor offset downwards Fig 16 Sensor offset to the r...

Страница 13: ...ction cable to KNX bus and auxiliary voltage Use the connection sockets and clips included for this purpose KNX bus Auxiliary votage red black yellow white Fig 17 1 Slide the device onto the mounting...

Страница 14: ...plied the device will enter an initialisation phase last ing approx 4 seconds During this phase no information can be received or sent via the bus 4 Addressing the equipment The equipment is delivered...

Страница 15: ...ion Suntracer KNX sl basic Status 26 08 2021 Errors excepted Subject to technical changes 1 Fig 19 1 Programming LED under the semi transparent lid 2 Programming button for teaching the device 2 botto...

Страница 16: ...ion Output R CT 1 1 DPT_Switch 1 bit 42 Temperature sensor External meas urement Input SK 9 1 DPT_Value_Temp 2 bytes 43 Temperature sensor Measurement value Output R CT 9 1 DPT_Value_Temp 2 bytes 44 T...

Страница 17: ...tes 69 Temp threshold value 3 Switching output Output R CT 1 1 DPT_Switch 1 bit 70 Temp threshold value 3 Switching output block Input WC 1 1 DPT_Switch 1 bit 72 Temp threshold value 4 Absolute value...

Страница 18: ...ue 3 1 0 Input WC 1 1 DPT_Switch 1 bit 117 Brightness sensor threshold value 3 Delay from 0 to 1 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 118 Brightness sensor threshold value 3 Delay from 1 to 0 Input...

Страница 19: ...lue 3 1 0 Input WC 1 1 DPT_Switch 1 bit 145 Brightness sensor 2 threshold value 3 Delay from 0 to 1 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 146 Brightness sensor 2 threshold value 3 Delay from 1 to 0...

Страница 20: ...ld value 3 1 0 Input WC 1 1 DPT_Switch 1 bit 173 Brightness sensor 3 threshold value 3 Delay from 0 to 1 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 174 Brightness sensor 3 threshold value 3 Delay from 1...

Страница 21: ...value 3 1 0 Input WC 1 1 DPT_Switch 1 bit 201 Total brightness threshold value 3 Delay from 0 to 1 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 202 Total brightness threshold value 3 Delay from 1 to 0 Inpu...

Страница 22: ...tch 1 bit 229 Twilight brightness threshold 3 delay from 0 to 1 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 230 Twilight brightness threshold 3 delay from 1 to 0 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 23...

Страница 23: ...Wind threshold value 2 Absolute value Input Output RWCT 9 5 DPT_Value_Wsp 2 bytes 288 Wind threshold value 2 1 0 Input WC 1 1 DPT_Switch 1 bit 289 Wind threshold value 2 Delay from 0 to 1 Input WC 7...

Страница 24: ...t R CT 4 bytes 1154 Computer 2 Condition text Output R CT 16 0 DPT_String_AS CII 14 bytes 1155 Computer 2 Monitoring status Output R CT 1 1 DPT_Switch 1 bit 1156 Computer 2 Block 1 block Input WC 1 1...

Страница 25: ...put RWCT 4 bytes 1192 Computer 7 Output O1 Output R CT 4 bytes 1193 Computer 7 Output O2 Output R CT 4 bytes 1194 Computer 7 Condition text Output R CT 16 0 DPT_String_AS CII 14 bytes 1195 Computer 7...

Страница 26: ...3 AND logic 4 1 bit switching output Output R CT 1 2 DPT_Bool 1 bit 1424 AND logic 4 8 bit output A Output R CT 1 byte 1425 AND logic 4 8 bit output B Output R CT 1 byte 1426 AND logic 4 Block Input W...

Страница 27: ...Input WC 1 1 DPT_Switch 1 bit 1455 OR logic 4 1 bit switching output Output R CT 1 2 DPT_Bool 1 bit 1456 OR logic 4 8 bit output A Output R CT 1 byte 1457 OR logic 4 8 bit output B Output R CT 1 byte...

Страница 28: ...ionally after changes i e at the beginning and end of a malfunction 6 1 General settings Set basic characteristics of data transfer A different transmission delay prevents an overload of the bus short...

Страница 29: ...cifying an offset e g in order to compensate malfunction sources Then set the mixed value calculation if desired Specify the send pattern for the total measured value Use rain output with fixed switch...

Страница 30: ...After power restoration and pro gramming should not be used for the initial start up as the factory settings are always used until the first call setting via objects is ignored Select whether the thre...

Страница 31: ...old value in 0 1 C valid until first call 300 800 200 Object value limit min in 0 1 C 300 800 Object value limit max in 0 1 C 300 800 Type of threshold change Absolute value Increase decrease Step siz...

Страница 32: ...object value before first call 0 1 Action when locking Do not send message send 0 send 1 Action upon release with 2 seconds release delay Dependent on the Switching output sends setting Switching outp...

Страница 33: ...frost on change and periodically on change to frost and periodically on change to no frost and periodically Send cycle if sent periodically 5 s 2 h 1 min Object value with frost 0 1 Sensor nomenclatur...

Страница 34: ...ed until the first call setting via objects is ignored Select whether the threshold value is to be specified per parameter or via a communi cation object When the threshold value per parameter is spec...

Страница 35: ...100 50 Hysteresis in Lux for absolute setting 0 150000 30000 When the following conditions apply the output is LV Threshold value GW above 1 GW Hyst below 0 GW above 0 GW Hyst below 1 GW below 1 GW H...

Страница 36: ...cts is ignored Select whether the threshold value is to be specified per parameter or via a communi cation object When the threshold value per parameter is specified then the value is set Switching ou...

Страница 37: ...in Lux 1 1000 Object value limit max in Lux 1 1000 Type of threshold change Absolute value Increase decrease Increment in Lux upon increase decrease change 1 2 5 10 20 50 Hysteresis setting in absolut...

Страница 38: ...ight and with which hysteresis this is to be outputted Action when locking do not send message send 0 send 1 Action upon release with 2 seconds release delay Dependent on the Switching output sends se...

Страница 39: ...set via objects in seconds No Yes Switching delay on night none 1 s 2 h Switching delay on day none 1 s 2 h Switching output sends on change on change to night on change to day on change and periodic...

Страница 40: ...and pro gramming should not be used for the initial start up as the factory settings are always used until the first call setting via objects is ignored Select whether the threshold value is to be spe...

Страница 41: ...0 1 m s valid until first call 1 350 40 Object value limit min in 0 1 m s incre ments 1 350 Object value limit max in 0 1 m s incre ments 1 350 Type of threshold change Absolute value Increase decreas...

Страница 42: ...power restoration and programming should not be used for the initial Use switching output block No Yes Analysis of the blocking object At value 1 block At value 0 release At value 0 block At value 1...

Страница 43: ...2 Prerequisite E1 E2 Prerequisite E1 E2 Prerequisite E1 E2 Prerequisite E1 E2 E3 Prerequisite E2 E1 E3 Prerequisite E1 E2 amount E3 Calculation E1 E2 Calculation E1 E2 Calculation E2 E1 Calculation E1...

Страница 44: ...0 Input range depending on the type of output if the condition is not met 0 Input range depending on the type of output if the monitoring time period is exceeded 0 Input range depending on the type o...

Страница 45: ...the monitoring status should have if the monitoring period is exceeded without feedback Output value if applicable A1 A2 if the monitoring time period is exceeded 0 Input range depending on the type...

Страница 46: ...ting options are available for AND and OR logic Monitoring period 5 s 2 h 1 min Value of the object monitoring status if period is exceeded 0 1 Use block No Yes Analysis of the blocking object At valu...

Страница 47: ...puts of the AND OR logic Output type a 1 Bit object two 8 bit objects Output value if logic 1 1 0 Output value if logic 0 1 0 Output value If block is active 1 0 Output value if monitoring period is e...

Страница 48: ...0 on change of logic and periodically on change of logic to 1 and periodically on change of logic to 0 and periodically on change of logic object receipt on change of logic object receipt and periodi...

Страница 49: ...input 11 Logic input 11 inverted Logic input 12 Logic input 12 inverted Logic input 13 Logic input 13 inverted Logic input 14 Logic input 14 inverted Logic input 15 Logic input 15 inverted Logic inpu...

Страница 50: ...2 Twilight inverted Switching output 3 Twilight Switching output 3 Twilight inverted Switching output 4 Twilight Switching output 4 Twilight inverted Wind switching output 1 Wind switching output 1 i...

Страница 51: ...49 Parameter setting Weather Station Suntracer KNX sl basic Version 26 08 2021 Technical changes and errors excepted AND logic output 8 inverted...

Страница 52: ...bH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www elsner elektronik de Technical support 49...

Отзывы: