20
Parameter settings
Temperature Sensor KNX T-UN
• Version: 27.01.2020 • Technical changes and errors excepted.
Frost/heat protection
Activate the frost/heat protection to set building protection mode of the heating/cool-
ing.
Set the setpoint for the heating and/or cooling. The building protection mode may be
activated with delay, which allows you to leave the building before the controls switch
to frost/heat protection mode.
5.6.
Logic
Activate the communication objects of the logic inputs if required. Then, activate the
required logic outputs.
AND logic
Limitation of object value H(max)\r\n
in 0.1°C
-300 … 800; 250
Start setpoint cooling in 0.1°C
valid until first call
(if the cooling regulator is being used and
only if the last retained value is "not"
retained, or retained "after power restora-
tion")
-300 … 800; 260
Limitation of object value C(min)\r\n
in 0.1°C
-300 … 800; 240
Limitation of object value C(max)\r\n
in 0.1°C
-300 … 800; 300
Type of setpoint value change
• Absolute value
• Increase / Decrease
Step size
(only when "increasing/decreasing")
0.1°C • 0.2°C • 0.3°C • 0.4°C • 0.5°C • 1°C •
2°C • 3°C • 4°C • 5°C
Use frost/heat protection
No • Yes
Setpoint heating in 0.1°C
(only if the heating regulator is being used)
-300 … 800; 70
Activation delay
(after opening windows)
no • 1 s • … • 5 min • ... • 2 h
Setpoint cooling in 0.1°C
(only if the cooling regulator is being used)
-300 … 800; 350
Activation delay
(after opening windows)
no • 1 s • … • 5 min • ... • 2 h
Window status before first call
Closed • Open
Communications objects logic inputs
not released • released
Logic 1 + 2 + 3 + 4
not active • active