13
Parameter settings
Temperature Sensor KNX T-UN
• Version: 27.01.2020 • Technical changes and errors excepted.
Block
The switching output can be blocked using an object. Define specifications here for the
behaviour of the output when blocked.
The behaviour of the switching output on release is dependent on the value of the pa-
rameter "Switching output sends" (see "Switching output")
5.5.
Temperature PI controller
Activate the controller if required.
General control
Then define the type of setting. Heating and/or cooling may be controlled in two stages.
Use temperature switching output block
No • Yes
Analysis of the temperature blocking object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Value of the temperature blocking object
before first call
0 • 1
Behaviour of the switching output
On block
• Do not send message
• send 0
• send 1
On release
(with 2 seconds release delay)
[Dependent on the "Switching output
sends" setting]
Switching output sends on change
• Do not send message
• Send switching output status
Switching output sends on change to 1
• Do not send message
• if switching output = 1
send 1
Switching output sends on change to 0
• Do not send message
• if switching output = 0
send 0
Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1 and
periodically
if switching output = 1
send 1
Switching output sends on change to 0 and
periodically
• if switching output = 0
send 0
Use controller
Yes • No
Type of control
• Single stage heating
• Dual-stage heating
• Single-stage cooling
• Single-stage h single-stage cooling
• Dual-stage h single-stage cooling
• Dual-stage h dual-stage cooling