Parameter settings
Temperature Sensor KNX T-UN
• Version: 27.01.2020 • Technical changes and errors excepted.
Then configure a temperature control block by the blocking object.
Specify when the current control variables are to be sent to the bus. Periodic transmis-
sion is safer if a message does not reach a recipient. You may also set up periodical
monitoring by the actuator with this setting.
Controller setpoint
Specified setpoint per parameter:
Set the setpoint.
Specifying a setpoint per communications object:
A starting setpoint value is defined as well as a temperature range in which the setpoint
value may be changed.
Behaviour of the blocking object with value
• 1 = Blocking regulation |
0 = Releasing regulation
• 0 = Blocking regulation |
1 = Releasing regulation
Blocking object value
before first call
0 • 1
Transmit control variable
• on change
• on change and periodically
Send cycle
(is sent only if "periodically" is selected)
5 s • … • 5 min • ... • 2 h
Specified setpoint using
Parameter • Communications object
Specified setpoint using
Parameter
Setpoint in 0.1°C
-300 … 800; 200
Specified setpoint using
Communications object
The last communicated value
should
• never be retained
• be retained after power restoration
• be retained after power restoration and
programming (not to be used for
first commissioning)
Start setpoint in 0.1 °C
valid until first call
(only if the last retained value is "not"
retained, or retained "after power restora-
tion")
-300 … 800; 200
Object value limit (min) in 0.1°C
-300 … 800; 140
Object value limit (max) in 0.1°C
-300 … 800; 250
Type of setpoint value change
• Absolute value
• Increase / Decrease
Step size
(only when "increasing/decreasing")
0.1°C • 0.2°C • 0.3°C • 0.4°C • 0.5°C • 1°C •
2°C • 3°C • 4°C • 5°C