Power Supply System 

KNX PS640+ 

with bus functions 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

         

 

 

 

 

 

 

 

 

 

Installation and Adjustment 

 

Elsner Elektronik GmbH

 Steuerungs- und Automatisierungstechnik 

Herdweg 7 • D-75391 Gechingen • Deutschland 

Phone.: +49 (0) 70 56/93 97-0 • Fax: +49 (0) 70 56/93 97-20 

[email protected] • www.elsner-elektronik.de 

Содержание KNX PS640+

Страница 1: ... functions Installation and Adjustment Elsner Elektronik GmbH Steuerungs und Automatisierungstechnik Herdweg 7 D 75391 Gechingen Deutschland Phone 49 0 70 56 93 97 0 Fax 49 0 70 56 93 97 20 info elsner elektronik de www elsner elektronik de ...

Страница 2: ...eset 6 Data memory 7 Operating data 8 Language 8 Transmission protocol 9 Abbreviations 9 Listing of all communication objects 9 Setting of parameters Software ETS 10 General settings 10 Messages 12 Current threshold value 14 KNX PS640 from software version 1 01 ETS programme version 1 1 Version 26 08 2009 Errors excepted Subject to technical changes ...

Страница 3: ...verload external overvoltage internal overvoltage short circuit and excess temperature Display of operating data bus voltage bus current and temperature of the device The display may be shown in German English Spanish or Dutch Bus connection for data transfer e g malfunction messages operating data Possibility for reset and diagnostics via the bus The programme file for KNX software ETS format VD2...

Страница 4: ...arried out by a competent electrician Disconnect all lines to be assembled and take safety precautions against accidental switch on The power supply is exclusively intended for appropriate use With each inappropriate change or non observance of the instructions for use any warranty or guarantee claim will be void After unpacking the device check immediately for any mechanical damages In case of tr...

Страница 5: ...ge power OUT KNX terminal 2 Programming LED and programming bushbutton 3 Bus data KNX terminal connection for line or main line or sector 4 Input operating voltage 230 V AC L N PE 5 Output direct current voltage 24 V DC Connections 4 and 5 are suitable for solid conductors up to 1 5 mm or conductors with fine wires Scheme Auxiliary supply 24 V DC max 150 mA ...

Страница 6: ...ine reset Move the cursor flashing rectangle at right edge to the desired setting with the keys or and confirm with key Yes Reset is activated The line is switched to neutral and shorted The basic setting displays Reset is active No Reset not activated The power supply system works in normal operation 30 seconds A reset of 30 seconds is started Afterwards the line is supplied with voltage as usual...

Страница 7: ...d With key you return to the previous menu level External Overvoltage The number of external overvoltage incidents is displayed With key you return to the previous menu level Internal Overvoltage The number of internal overvoltage incidents is displayed With key you return to the previous menu level Short circuit Excess Temperat Hours ofOperation Overload Ext Overvoltage Int Overvoltage Run time 0...

Страница 8: ...of Bus voltage Bus current Temperature on the circuit board of the device are displayed With key you return to the previous menu level Language In starting position press key once Move the cursor flashing rectangle at right edge to the Language menu with the keys and and confirm with the key Bus Voltage 29 4 V Bus Current 320 mA Temperature 42 1 C A short at the bus was detected 0 times Back Exces...

Страница 9: ... Time reset 1 30 seconds active 0 inactive Input 1 003 C R W 4 Reset status of the line 1 active 0 inactive Output 1 002 C R T 5 Overload 0 normal 1 overload Output 1 002 C R T 6 external overvoltage 0 normal 1 overvoltage Output 1 002 C R T 7 internal overvoltage 0 normal 1 overvoltage Output 1 002 C R T 8 Short circuit 0 normal 1 short circuit Output 1 002 C R T 9 Overtemperature 0 normal 1 over...

Страница 10: ... 000 C R T 20 Threshold value 16 bit value mA Input Output 9 021 C R W T U 21 Threshold value 1 Increment 0 Decrement Input 1 008 C R W 22 Threshold value Increment Input 1 017 C R W 23 Threshold value Decrement Input 1 017 C R W 24 Threshold value Switching output Output 1 002 C R T 25 Threshold value Switching output block Input 1 003 C R W 26 Software version readable 217 001 C R Setting of par...

Страница 11: ...in case of change send in case of change and cyclically Sending cycle only if sending cyclically 5 sec 10 sec 30 sec 1 min 2 h Change in only if sending in case of change 1 100 Reset of the linie What shall be used for the reset display and keyboard Yes object permanent reset 1 reset 0 no reset No Yes object time reset 1 30 seconds reset 0 no reset No Yes Use object reset status of the line No Yes...

Страница 12: ... cyclically Sending cycle only if sending cyclically 5 sec 10 sec 30 sec 1 min 2 h Object external overvoltage The setting options are similar to object overload Object internal overvoltage The setting options are similar to object overload Object short circuit The setting options are similar to object overload Object overtemperature The setting options are similar to object overload Object system...

Страница 13: ... Object 8 bit status collection do not send send in case of change send in case of change and cyclically Sending cycle only if sending cyclically 5 sec 10 sec 30 sec 1 min 2 h Bit 0 reset status of the linie Bit 1 overload Bit 2 external overvoltage Bit 3 internal overvoltage Bit 4 short circuit Bit 5 overtemperature Bit 6 current threshold value exceeded Bit 7 system defect Error log Use error lo...

Страница 14: ...reshold value in 0 50 If the threshold value is set by communication object Threshold value is set by Communication object The value communicated last shall be maintained not after restoration of voltage after restoration of voltage and programming Do not use for first commissioning Start threshold value in mA valid until 1 communication only if the value communicated last is not maintained or aft...

Страница 15: ... s 5 s 10 s 2 h Switching output sends send in case of change send in case of change to 1 send in case of change to 0 send in case of change and cyclically send in case of change to 1 and cyclically send in case of change to 0 and cyclically Send switching output in a cycle of only if sending cyclically 5 sec 10 sec 30 sec 1 min 2 h Blocking Use block of the switching output No Yes If the block of...

Страница 16: ... change do not send telegram send status of the switching output in case of change to 1 do not send telegram if switching output 1 send 1 in case of change to 0 do not send telegram if switching output 0 send 0 in case of change and cyclically send status of the switching output no selection in case of change to 1 and cyclically if switching output 1 send 1 no selection in case of change to 0 and ...