10
No. Name
Function
EIS type
Flags
15
Recall error information
(1 = No.+1 | 0 = No.-1)
Input
1.008
C R W
16
Message part 1
Output
16.000
C R T
17
Message part 2
Output
16.000
C R T
18
Message part 3
Output
16.000
C R T
19
Message part 4
Output
16.000
C R T
20
Threshold value: 16 bit value [mA]
Input / Output
9.021
C R W T U
21
Threshold value:
1 = Increment | 0 = Decrement
Input
1.008
C R W
22
Threshold value: Increment
Input
1.017
C R W
23
Threshold value: Decrement
Input
1.017
C R W
24
Threshold value: Switching output
Output
1.002
C R T
25
Threshold value: Switching output block
Input
1.003
C R W
26
Software version
readable
217.001
C R
Setting of parameters (Software ETS)
General settings